Effect of magnetic field on the performance of new refrigerant mixtures


INTERNATIONAL JOURNAL OF ENERGY RESEARCH
Int. J. Energy Res. 2003; 27: 203 214 (DOI: 10.1002/er.868)
Effect of magnetic field on the performance of
new refrigerant mixtures
Samuel M. Samin,y and Shawn Aucoinz
Mechanical Engineering, School of Engineering, University of Moncton, Moncton, NB, E1A 3E9, Canada
SUMMARY
Performance test results of new alternative refrigerant mixtures such as R-410A, R-507, R-407C, and
R-404A under various conditions of magnetic field are discussed, analysed and presented. The test results
were obtained using an air-source heat pump set-up with enhanced surface tubing under various magnetic
field conditions. Performance tests were conducted according to the ARI/ASHRAE Standards.
The test results demonstrated that as magnetic field force increases, compressor head pressure and
discharge temperature slightly increase as well as less liquid refrigerant is boiling in the compressor shell.
This has a positive effect in protecting the compressor. The effect of magnetic field on mixture behaviour
varies from one mixture to another depending upon the mixture s composition and its boiling point.
Furthermore, the use of magnetic field appears to have a positive influence on the system COP as well as
thermal capacities of condenser and evaporator. Copyright # 2002 John Wiley & Sons, Ltd.
KEY WORDS: new refrigerant mixtures; magnetic caloric effect; ARI/ASHRAE standards
1. INTRODUCTION
It is well known that certain materials properties and particularly temperature will increase
when placed in a magnetic field and, will likewise decrease when the magnetic field is removed.
This mainly is caused by the effect of the magnetic field on the entropy and the heat content of
material. This phenomenon is known as magnetic caloric effect. The effect of magnetism and
magnetic field on fluids is still considered as not well-known subject. However, it is well
established that there are major changes caused by the passage of fluid through magnetic field.
Several magnetic refrigeration devices under development by Astronautics using convention
NbTi magnets have been described by Zimm and De Gregoria (1992). The system advantages of
incorporating high-temperature super conducting magnets in designs have been discussed. The
authors also explained the nature of active magnetic regenerative (AMR) cycle and its
requirements in refrigeration.
n
Correspondence to: S.M. Sami, Mechanical Engineering, School of Engineering, University of Moncton, Moncton,
NB, E1A 3E9, Canada.
y
Professor and Director of the Research Centre for Energy Conversion.
z
Research Assistant.
Contract/grant sponsor: NSERC.
Contract/grant sponsor: University of Moncton.
Received 9 April 2002
Copyright # 2002 John Wiley & Sons, Ltd. Accepted 5 June 2002
204 S.M. SAMI AND S. AUCOIN
Research on magnetic caloric effect and its application have been discussed by Gschneiddd-
ner and Pecharsky (1999) for cooling near-room temperature. The study included the
relationship between the nature of magnetic transformation and the temperature dependence
of the magnetic caloric effect and the entropy utilized in the magneto caloric.
The magnetic measurements to evaluate the thermodynamic behaviour of magnetic material
have been presented by Foldeaki et al. (1995). As reported in this reference, depending on the
thermodynamic cycle selected, the isothermal magnetic entropy temperature change or the
adiabatic temperature change upon the field application should be preselected as a function of
temperature. This paper presented classical magnetic measurements, when evaluated within the
framework of the Landau theory.
A magnetic heat pumping can be made according to Brown (1976) using a ferromagnetic
material with a curie point and an appropriate thermodynamic cycle. The regenerative magnetic
cycle can approach the Carnot cycle efficiency, as reported by Brown.
Furthermore, most refrigeration and air-conditioning systems experience load variation. High
efficiency and high performance are greatly in demand. Among techniques employed for
improvement, capacity control, optimization of vapour compression systems are the refrigerant
liquid and vapour injection. However, it is believed that the magnetic field can be employed as
an enhancing technique.
The several studies reported in the literature demonstrated the magnetic field and its
capabilities as well as its impact on the thermodynamic characteristics. However, as the EHD
technique has shown an improvement of the heat transfer on refrigerant side (Muraki et al.,
2001), it is believed that magnetic field could have an enhancement effect on heat transfer
properties. Several studies have been reported on the use of magnetic elements in enhancing the
performance in many applications such as oil, natural gas furnaces, diesel engines, fuel lines and
also in water treatment. To the authors knowledge none has been reported on the use of
magnets as a performance enhancer in the refrigeration industry.
Therefore, this paper is concerned with the study and analysis of some refrigerant mixtures
behaviour inside enhanced surface tubing air fined heat exchangers under magnetic field at
various forces of the magnetic field (Gauss levels). The blends under consideration in this study
are; R-507 (R-125/R-143a:50/50%), R-404A (R-125/R-143a/R-134a:44/52/4%), R-410A (R-32/
R-125:50/50%), and R-407C (R-32/R-125/R-134a:23/25/52%). All percentages of the afore-
mentioned blends are based on weight. The main thrust of this study is to study the
enhancement of the heat transfer rates and system coefficient of performance and optimize the
use of magnets in refrigeration systems.
2. EXPERIMENTAL APPARATUS AND MEASUREMENTS
Figure 1 shows a schematic diagram of the experimental set-up, which is an air-source vapour
compression heat pump, composed mainly of a 3 kW compressor, oil separator, condenser,
precondenser, pre-evaporator, adjustable expansion device, capillary tubes and evaporator.
Three magnetic elements with Gauss level of 4000 each have been employed in this study.
These magnets were intended for gasoline fuel line of 1/4 in diameter, they were clamped at the
refrigerant line of same diameter. The units were single-type with two brackets strapped around
the pipe. They were clamped on the refrigerant liquid line at the post-condenser outlet at various
distances, before the capillary tube/thermal expansion valve used as flow control device. During
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214
EFFECT OF MAGNETIC FIELD ON REFRIGERANT MIXTURES 205
Figure 1. Schematic diagram of the air/air heat pump test facility.
the course of this experimental study, series of three magnets were used totalling 12 000 Gauss
levels. The magnets were placed at three locations of the post-condenser outlet at a distance of
0.13, 0.47 and 0.71 m, respectively. This was necessary to ensure that the magnets are placed on
the refrigerant full liquid line. This is confirmed by observation through the sight glass. At each
position, experiments were conducted with one, two and three magnets placed at 0.01 m spacing
between each other. Figure 1 depicts the set-up flow diagram and magnet positions.
The oil content in the refrigerant loop was estimated to be about 1% using gas
chromatography. Pressure, temperature and flow rate measuring stations are shown in
Figure 1. All pressures were measured using calibrated pressure transducers (0 800 kPa). The
accuracy of the pressure transducers was 2.5%. Differential pressure transducers were
employed to measure the refrigerant flow rate. Temperatures were measured by RTD
temperature sensors which have an accuracy of 0.5%. Humidity measurements were
obtained through the accurate recording of dry and wet bulb temperatures.
All recorded measurements were obtained at a variable sink and source air temperature of
218C entering the condenser. On the other hand, the capillary tubes were adjusted to optimize
the system s performance with every tested refrigerant mixture. This simulates the system s
performance at different thermal loads and using a variable thermal expansion valve.
A calibrated orifice, installed in the liquid refrigerant line after a liquid receiver, was used to
measure the refrigerant mass flow rate. Pressure taps on both sides of the orifice were connected
to a differential pressure transducer (0 250 kPa). Air mass flow rate was also measured by a
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214
206 S.M. SAMI AND S. AUCOIN
Pitot tube-type air flow meter calibrated station. The accuracy of the mass flow measurements
was 3% of the nominal flow.
Power supplied to the compressor was measured because it is needed for the heat balance. An
AC/DC clamp-on was calibrated for power measurements with an accuracy of 3%. The
energy balance of the test unit was within 3%.
Data collection was carried out using a P150 equipped with a data acquisition system with a
capacity of 112 channels. This enabled us to record, at a single scan the local properties such as:
pressure drops, pressure, temperature, and flow rates as well as power consumption.
All tests of the blends under question were preformed under steady-state conditions and
according to ANSI/ASHRAE 37-1978 Standard and ARI-240 Standard. The data collection
was scanned every second and stored every 10 s. The experimental values were averaged over a
period of 10 s.
The primary parameters observed during the course of this study were: mass flux, heat
flux, thermal capacities, power consumed and quality for refrigerants under investigation;
R-507, R-404A, R-407C as well as R-410A at various magnetic element conditions. It is
important to note that during the course of this study the impact of each magnetic condition
was tested separately and measurements were only recorded once the system reached a stable
condition.
In order to evaluate the blend s performance, the thermodynamic properties of pure and
zeotropic refrigerant mixtures should be known. REFPROP (McLinden et al., 1998) version
6.01 was used to evaluate the mixture s characteristics. Interaction parameters were selected
with caution, since their values may influence the outcome of REFPROP prediction of the
thermodynamic and transport properties. Interaction parameters are the mixing parameters of
refrigerant mixtures.
Test conditions and coil specifications of the heat exchangers used employed in this study are
given in Tables I and II. The geometrical parameters of the micro-fin tubes are also presented in
Table III.
Table I. Air coils specifications.
Tube outer diameter 3/800
Rows deep 4
Fin per inch 12
Fin depth 3.4600
Fin height 2000
Fin length 3000
Fin thickness 0.004500
Rifled tubes Microfins
Table II. Test conditions.
Temperature of air of the condenser inlet 218C
Temperature of air at the evaporator inlet 15 to +88C
Air flow rate 7.07 10 2 9.4 10 2 m3 s 1
Refrigerant mass flow rate 8 40 g s 1
Condenser pressure 600 1800 kPa
Evaporator pressure 170 450 kPa
Standard relative humidity at condenser inlet 45%
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214
EFFECT OF MAGNETIC FIELD ON REFRIGERANT MIXTURES 207
Table III. Geometry of micro-fin tubes, (round tip geometry).
Outside diameter 0.37500
Root diameter 0.34400
Tip diameter 0.33100
Fin height 0.007400
Pitch 0.01600
3. RESULTS AND DISCUSSION
In the following sections, samples of the system s performance with some new alternative
refrigerants under various magnetic fields conditions will be presented, discussed and analysed.
The test conditions were: condenser pressure varied between 600 and 1800 kPa, and the
condenser refrigerant temperature was between 28 and 388C. The evaporator pressure ranged
from 170 to 450 kPa, and the refrigerant evaporator temperature was between 20 and 68C.
Under these conditions, and at each test, the following parameters have been measured: thermal
capacities at evaporator and condenser sides, power consumed by compressor, refrigerant flow
rates, coolant flow rates and refrigerant quality at both evaporator and condenser sides.
The aforementioned measured/calculated parameters, such as power consumed and thermal
capacities at the evaporator and condenser, are necessary for evaluating the coefficient of
performance (COP) under heating and cooling modes. However, only the heating mode was
considered in this study.
The COP and heat absorbed/released at system heat exchangers are calculated as follows:
Heat absorbed=released
COP ź ð1Þ
Compressor power
and

Qa=r ź mf Cp;f DT ð2Þ
m

Qa=r ź mf DH ð3Þ
m

where mf and DT represent the air mass flow rate, and air temperature difference across the
m
evaporator/condenser coils. Cp;f is the specific heat for airflow and DH gives the total air
enthalpy difference across the heat exchangers.
Equations (2) and (3) represent the heat exchanger sensible and latent heats, respectively.
Equation (3) is employed particularly during cooling load calculation.
As mentioned during the course of this study, only heating tests were conducted. There-
fore, only the sensible heat was considered in calculating the thermal capacities as shown in
Equation (2).
The results of the various refrigerant mixtures with no magnets were used as a baseline for this
study. Upon completion of the baseline results of each refrigerant mixture, under the
aforementioned conditions, the compressor and the system was drained and evacuated.
Following this step, the system was then recharged with the preferred refrigerant mixture. This
procedure was repeated before conducting the series of tests for every single alternative mixture.
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214
208 S.M. SAMI AND S. AUCOIN
Figure 2. Condenser COP vs evaporator inlet air temperature with no magnets.
In the following, the functional dependence of the following parameters on the refrigerant
temperature entering the evaporator will be outlined; input power, thermal heating capacity at
the condenser side, pressure ratio, condenser pressure, evaporator thermal capacity and COP.
During the experimentation, the sink s air temperature was kept constant at 218C, and
relative humidity was also kept at 45%. The source coolant temperature varied from 15 to 58C
at the evaporator inlet. The dry and wet bulb temperatures of the source and sink were within
the ASHRAE and ARI Standards.
Samples of the results obtained during these runs and used as baseline data with no magnets
were plotted in Figure 2 at various entering air temperatures to the evaporator. As expected, the
results plotted in this figure show that the COP heating, increases at higher entering air
temperature at the evaporator side. The results also demonstrate that R-404A has the highest
COP among the mixtures under investigation.
In order to study the influence of the number of magnets on the behaviour of the refrigerant
mixtures and the system performance samples of the test, results were plotted at various
conditions in Figures 3 12. On the other hand, it appears from the sample results displayed that
the magnets accelerated the increase of the COP compared to the no magnets results.
Furthermore, R-404A appears to show the highest performance at lower evaporation
temperatures and this is mainly due to its significant latent heat at low temperatures.
It is quite clear from Figure 4 that the evaporator COP was enhanced with different
percentages depending on the type of mixture and its boiling point. This has a positive and
significant impact on the cooling capacity as well as the efficiency of the system performance. It
is quite clear from the data in Figure 4 that R-507 behaviour is significantly influenced by the
magnetic field force (Gauss levels) and power of the magnets. On the average, it appears that
higher Gauss levels enhanced the evaporator COP by 20% depending upon the refrigerant
mixture boiling point. It is believed that the magnetic effect or field changes the polarity of oil
which is a hydrocarbon from negative charge to positive charge. This results in entertaining the
oil and being carried away from the heat transfer surface, thus enhancing the heat transfer rate
and coefficient of heat transfer. Thus, the consequent effect on the COP has been caused by this
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214
EFFECT OF MAGNETIC FIELD ON REFRIGERANT MIXTURES 209
Figure 3. Condenser COP vs number of magnetic elements at constant temperature (08C).
Figure 4. Evaporator COP vs number of magnetic elements at constant temperature (08C).
phenomenon. It was also shown that higher Gauss levels increase thermal capacities. Previous
studies have shown that oil entertained in the refrigerant flow results in degrading the heat
transfer rates (Sami et al., 1993).
Furthermore, since the condenser s COP is an important parameter in evaluating the cycle
performance, and is calculated as function of the compressor power, Figure 5 has been
constructed to show the impact of the magnet Gauss levels on the power consumed. It appears
that the magnets reduce slightly the power consumption of the compressor. Also higher Gauss
levels results in decreasing the power consumption. The decrease of the power consumption
appear to be around 8%. It is believed that increasing Gauss levels decreases the compressor
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214
210 S.M. SAMI AND S. AUCOIN
Figure 5. Compressor capacity vs number of magnetic elements at constant temperature (08C).
Figure 6. Condenser capacity vs number of magnetic elements at constant temperature (08C).
power and therefore enhance the COP. This is a result of efficient boiling and condensation and
less liquid being boiled at the compressor shell. It is interesting to note that the mixtures with
higher latent heat seem to exhibit slower decrease in the power consumption.
In order to understand the impact of the magnetic field on the condenser capacity, Figure 6
has been plotted for the refrigerant mixture in question. Slight increase in the condenser capacity
was observed. However, R 410-A showed the highest increase in capacity with the increase of
Gauss levels.
Figure 7 shows the evaporator capacity under various Gauss levels. The data presented in this
figure clearly demonstrated the enhancement of the evaporator capacity with the increase in the
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214
EFFECT OF MAGNETIC FIELD ON REFRIGERANT MIXTURES 211
Figure 7. Evaporator capacity vs number of magnetic elements at constant temperature (08C).
Figure 8. Pressure ratio vs number of magnetic elements at constant temperature (58C).
number of magnetic elements used. It also appears that the R-404A experiences the highest
enhancement among the refrigerant mixtures under investigation. This is mainly due to the low
boiling temperature of the mixture and the high latent heat at the test temperature.
The pressure ratio represents the ratio between the discharge and the suction pressure across
the compressor. Figure 8 displays results observed with various magnetic element. The results
show that the pressure ratio has been slightly increased with the increase in the number of
magnetic elements. This is expected since less liquid refrigerant is being boiled in the compressor
shell and therefore, this results in increasing the pressure ratio. This trend has been observed
with other refrigerant mixtures under investigation.
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214
212 S.M. SAMI AND S. AUCOIN
Figure 9. Compressor discharge pressure vs number of magnetic elements at constant temperature (08C).
Figure 10. Compressor capacity vs number of magnetic elements of constant temperature ( 158C).
The compressor head pressure and discharge temperature are important parameters to be
considered when selecting an alternative mixture, therefore, Figure 9 has been constructed to
study these parameters. Figures 4 6 gives clear evidence that as the magnetic field force increases
COP of the condenser and evaporator increase. However, it also appears that higher Gauss
levels slightly decrease the discharge pressure. It is suggested that this is a result of less liquid
refrigerant being carried into the compressor chamber. Furthermore, these results clearly
indicate that R-410A has superior compression properties compared to the other blends under
investigation.
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214
EFFECT OF MAGNETIC FIELD ON REFRIGERANT MIXTURES 213
Figure 11. Condenser capacity vs number of magnetic elements of constant temperature ( 158C).
Figure 12. Evaporator capacity vs number of magnetic elements of constant temperature ( 108C).
Based on the above results and the additional information presented in Figures 4 6, it appears
from Figure 10 that lower evaporation temperatures seem to slightly increase the compressor
capacity with higher Gauss levels. This is quite expected since higher Gauss levels enhance the
evaporator capacity and therefore, reduce refrigerant liquid boiling in the compressor shell. Figure 11
also demonstrates that higher magnetic fields results in enhancing the heating capacity of the
system even at low evaporation temperatures. This figure also shows that the refrigerant mixture
in question respond similarly to the increase of the magnetic field force. Figure 12 displays
sample results on the impact of magnetic field force on the cooling capacity of the evaporator.
Refrigerant mixture exhibit almost the same behaviour with increase of magnetic field levels
however, it appears that R-507 experienced slight decrease in the evaporator capacity.
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214
214 S.M. SAMI AND S. AUCOIN
4. CONCLUSIONS
During the course of this experimental study, the performance characteristics of some new
proposed substitutes under various magnetic field levels have been investigated, analysed and
compared to that of no magnet condition. The test results under heating conditions
demonstrated that increasing the magnet capacity has a positive effect on the COP. The study
showed that the effect of magnetic field on the mixture behaviour varied depending upon the
mixture s composition and its boiling point.
ACKNOWLEDGEMENTS
The research work presented in this paper was possible through grants from NSERC. The authors wish to
acknowledge the continuous support of the University of Moncton.
REFERENCES
Brown GV. 1976. Magnetic heat pumping near room temperature. Journal of Applied Physics 47(8):3673 3680.
Foldeaki M, Chahine R, Bose TK. 1995. Magnetic measurements: A powerful tool in magnetic refrigerator design.
Journal of Applied Physics 77(7):3528 3537.
Gschneidddner KA, Pecharsky VK. 1999. Magnetic refrigeration materials. Journal of Applied Physics 85(8):5365 5368.
McLinden MO et al. 1998. NIST Thermodynamic and Transport Properties of Refrigerants Mixtures REFPROP, Version
6.0. NBS: Gaithersburg, MD.
Muraki M, Sano T, Dong D. 2001. Rheological properties of polyolester under an EHD contact in some refrigerant
environments. Journal of Tribology 123(1):54 60.
Sami SM, Tulej PJ, Fang L. 1993. Heat transfer in forced convection boiling of oil non-azeotropic binary refrigerant
mixtures. International Journal of Energy Research 17:903.
Zimm CB, DeGrgoria AJ. 1992. Magnetic refrigeration: Application and enabler for HSTC magnets. AIP Conference
Proceedings, vol. 273(1), 10 February 1992, 471 480.
Copyright # 2002 John Wiley & Sons, Ltd. Int. J. Energy Res. 2003; 27:203 214


Wyszukiwarka

Podobne podstrony:
Real gas effects on the prediction of ram accelerator performance
The effects of context on incidental vocabulary learning
22 THE EFFECTS OF RADIATION ON THE HUMAN BODY
The Effects of Caffeine on Sleep in Drosophila Require PKA
THE EFFECT OF WELFARE ON WORK AND MARRIAGE
The Effects of Vias on PCB Traces
Ando An Evaluation Of The Effects Of Scattered Reflections In A Sound Field
Curseu, Schruijer The Effects of Framing on Inter group Negotiation
Effects of kinesio taping on proprioception at the ankle
effect of varying doses of caffeine on life span D melanogaster
Dennett Facing Backwards on the Problem of Consciousness
Radiative Ignition of Pyrotechnics Effect of Wavelength on Ignition Threshold
Dijksterhuis On the benefits of thinking unconsciously
Yifeng, Tjosvold Effects of warm heartedness and reward distribution on
Research into the Effect of Loosening in Failed Rock
Logan; Newman and Rahner on the Way of Faith – and Wittgenstein come too
J B O Always look on the?rk side of live
Anderson, Kevin J Music Played on the Strings of Time

więcej podobnych podstron