mitsubishi mr slim error codes


OC121--2.qxp 24/6/97 2:18 AM Page 42
airconwarehouse.com - Mitsubishi Mr. Slim Error Codes - Membrane type remote controllers
Check
Diagnosis of malfunction Cause Check points
code
Signal transmitting/receiving During individual unit control 1) Check the transmission wire.
EO
error 1) Bad contact of transmission 2) Check with another remote controller. If  EO is
(Indoor controller does not wire still indicated, replace the indoor controller
respond to remote controller 2) Signal transmitting/receiving cir- board.
signal.) cuit is abnormal. If other check code appears. replace the origi-
nal remote controller.
Abnormality of room temper- 1) Bad contact of thermistor 1) Check the thermistor.
P1
ature thermistor (RT1) 2) Damaged thermistor 2) Measure the resistance of the thermistor.
Normal resistance should be as follows.
32°F····15k&! 86°F·····4.3k&!
50°F······9.6k&! 104°F·····3.0k&!
68°F······6.3k&!
Abnormality of indoor coil
P2
If the resistance is normal, replace the indoor
thermistor (RT2)
controller board.
Signal transmission error 1) Bad contact of transmission 1) Check the transmission wire.
P3
(Remote controller does not wire 2) Check with another remote controller.
respond to indoor controller 2) Signal transmitting/receiving cir- If  P3 is still indicated, replace the indoor
signal.) cuit is abnormal. board.
3) Wrong operation due to noise If other check code appears, replace the origi-
wave emitted by other appli- nal remote controller.
ances 3) Short-circuit between and of CN40 and
attach CN40 to the following units.
Second unit in twin control
Second and third units in triple control
Sub units in group control
Abnormality of drain sensor 1) Bad contact of transmission 1) Check the connector.
P4
wire 2) Measure the resistance of the thermistor - .
2) Damaged thermistor As for the normal resistance, refer to the case
of P1.
If the resistance is normal, replace the indoor con-
troller board.
Malfunction of drain pump 1) Malfunction of drain pump 1) Check the drain pump.
P5
2) Damaged drain sensor 2) Check the drain sensor.
Check the drain sensor heater. Normal resis-
tance should be 82&!.
If the resistance is normal, replace the indoor con-
troller board.
Coil frost protection is work- 1) Short cycle of air cycle 1) Clear obstructions from the air cycle.
P6
ing. 2) Dirty air filter 2) Clean the air filter
3) Damaged fan 3) Check the fan.
4) Abnormal refrigerant 4) Check the refrigerant temperature.
1) Wrong address-setting 1) Check the address-setting.
P7
System error 2) Signal transmitting/receiving cir- 2) Check with another remote controller. If check
cuit of remote controller is code other than  P7 appears, replace the origi-
abnormal. nal remote controller.
3) Wrong SW6-setting 3) Check SW6 setting.
Abnormality in outdoor unit 1) Wrong wiring of indoor/outdoor 1) Check the indoor/outdoor connecting wire.
P8
connecting wire 2) Change the connection of electric wiring.
2) Reversed phase 3) Check the protection device.
3) Protection device is working 4) Measure the resistance of the outdoor coil ther-
4) Damaged outdoor coil thermis- mistor. If the resistance is normal, replace the
tor outdoor controller board.
42


Wyszukiwarka

Podobne podstrony:
Hitachi error codes
amicaPC Error codes
Fujitsu error codes old
tsa macroparser ERROR CODES
error codes
Windows Error Codes
Mitsubishi?ult Codes
function mysql error
Kelis Mr UFO Man
IHK codes
error
function error reporting
old error handler
Kody Fault Codes Whirpool
jh error utf8

więcej podobnych podstron