02 ZELIO TIME CATALOGUE


<< Back
<< Back
<< Back
<< Back
RE 1 timing relays
Solid state output, width 17.5 mm
References :
page 28411/3 Characteristics
Dimensions, schemes :
page 28411/4
Compatibility :
page 28411/5
Type RE1-LA (On-delay) RE1-LC (Off-delay)
Environment
Conforming to standards IEC 144, 158-1 and 255-5, NF C 20-010, 20-040 and 63-030, VDE 0110 C
and EN 50005
Product certifications CSA, NEMKO, SEMKO, BV NEMKO, BV
Protective treatment  TH  TH
Ambient air temperature Operation C - 25& + 60 - 25& + 60
around the device Storage C - 40& + 85 - 40& + 85
Rated insulation voltage (Ui) Conforming to IEC 158-1 and CSA V IEC 158-1 : 250; CSA : 300 IEC 158-1 : 250 ; CSA : 300
Vibration resistance Severity A 55 55
Conforming to NF C 20-616 & IEC 68-2-6 Permissible acceleration 5 gn (60& 500 Hz) 5 gn (60& 500 Hz)
Shock resistance Severity A 50 50
Conforming to NF C 20-608 Permissible acceleration 50 gn (pulse duration 11 ms) 50 gn (pulse duration 11 ms)
Degree of protection IP 40 IP 40
Maximum operating altitude Without derating m 3000 3000
Operating positions Without derating Any position Any position
Cabling Using cable mm2 1 x 0.75 to 2 x 1.5, with or without cable end; captive screw clamps
Using Faston connectors 2 x 2.8 or 2 x 6.35
Using open or closed tags Removable screw clamps
Control circuit characteristics
Supply voltage And permissible variation V c and a 24& 240; 0.8& 1.1 Un c 24& 240; 0.8& 1.1 Un
Frequency And permissible variation Hz 50/60 ą 20 % 50/60 ą 20 %
Control contact Hard-wired connection only  RE1-LC : connecting cable
to timer d" 10 m
Time delay characteristics
Timing range 0.1& 3 s; 1& 30 s; 10& 300 s; 2& 60 min
Setting accuracy 0.1& 300 s : d" 10 % of the full scale
2& 60 min : d" 15 % of the full scale
Repeat accuracy Conforming to VDE 0435 ą 3 % (0& 40 C) ą 3 % (0& 40 C)
Reset time Range from 0.1& 300 s ms 150 (25 after the time delay) 200
during the time delay period Range from 2& 60 min ms 650 (25 after the time delay) 1600
Maximum immunity to Range from 0.1& 300 s ms 10 (2 after the time delay) 20
micro-breaks during
the time delay period Range from 2& 60 min ms 200 (2 after the time delay) 200
Time delay indication By integral LED LED illuminates during the time delay period
Switching characteristics (solid state type)
Maximum continuous current At ambient  : 20 C A 0.7 (minimum 10 mA) 0.7 (minimum 10 mA)
Maximum short time rating For 10 ms A 15 15
Volt drop,  closed state V 3 max to 0.7 A 3 max to 0.7 A
Leakage current  open state m A d" 5 d" 1
Maximum power loss W 2.5 4
Derating For temperature > 20 C mA 5 per C 5 per C
Overload protection Conforming to IEC 255-5 3 kV 0.5 joule 3 kV 0.5 joule
In millions of
Electrical durability operating cycles 100 100
28411/2
Te
RE 1 timing relays
Solid state output, width 17.5 mm
Characteristics :
c
page 28411/2 References
or
Dimensions, schemes :
page 28411/4
a
Compatibility :
page 28411/5
On-delay timers
Type of Type of Timing Reference Weight
circuit connection range kg
a.c. or d.c. For cable 1 x 0.75 to 2 x 1.5 mm2 0.1& 3 s RE1-LA001 0.055
24& 240 V with or without cable end,
recessed +/- screw clamp 1& 30 s RE1-LA002 0.055
terminals.
10& 300 s RE1-LA003 0.055
2& 60 min RE1-LA004 0.055
For open or closed tags 0.1& 3 s RE1-LA301 0.055
recessed +/- screw clamp
terminals. 1& 30 s RE1-LA302 0.055
10& 300 s RE1-LA303 0.055
RE1-LA001
2& 60 min RE1-LA304 0.055
For Faston connectors 2 x 2.8 0.1& 3 s RE1-LA101 0.055
or 2 x 6.35
1& 30 s RE1-LA102 0.055
I0061/2
10& 300 s RE1-LA103 0.055
2& 60 min RE1-LA104 0.055
Off-delay timers
a.c. For cable 1 x 0.75 to 2 x 1.5 mm2 0.1& 3 s RE1-LC011 0.055
24& 240 V with or without cable end,
recessed +/- screw clamp 1& 30 s RE1-LC012 0.055
RE1-LA301 terminals.
10& 300 s RE1-LC013 0.055
2& 60 min RE1-LC014 0.055
For open or closed tags 0.1& 3 s RE1-LC311 0.055
recessed +/- screw clamp
terminals. 1& 30 s RE1-LC312 0.055
10& 300 s RE1-LC313 0.055
2& 60 min RE1-LC314 0.055
For Faston connectors 2 x 2.8 0.1& 3 s RE1-LC111 0.055
or 2 x 6.35
1& 30 s RE1-LC112 0.055
RE1-LC013 10& 300 s RE1-LC113 0.055
2& 60 min RE1-LC114 0.055
Accessories (to be ordered separately)
Description Sold in Unit Weight
lots of reference kg
Lead sealing kit 10 LA9-RE01 0.005
Mounting plate For M4 screws, 40 mm centres 10 AM1-PT01 0.020
Clip-in markers Strip of 10 identical 25 AB1-R (1) 0.002
(5 max. per numbers (0 to 9)
timer)
Strip of 10 identical 25 AB1-G (1) 0.002
RE1-LC112 capital letters (A to Z)
(1) To order, add the required number or letter to the end of the reference.
Other versions Cabling by captive or removable screw clamp connections; Faston connectors.
For other information : bulk purchase, prices, delivery times, please consult your Regional Sales
Office.
28411/3
Te
RE 1 timing relays
Solid state output, width 17.5 mm
Characteristics :
Dimensions, mounting, schemes
page 28411/2
References :
page 28411/3
Compatibility :
page 28411/5
Dimensions and mounting methods for timers RE1-LA and LC
Mounting on AM1-DP200, AM1-DE200 rail Mounting with plate AM1-PT01
2x4
15 38 17,5 15 38 17,5
(1) 60
(1) 60 with AM1-DP, 67.5 with AM1-DE.
Wiring schemes
Caution : The terminal references enclosed in brackets refer to old version electronic timers.
RE1-LA On-delay
The timer is connected in series between the load which
K A1 L A1 A2
requires delayed energisation and switch K. The mains
(1) (2)
supply can be a.c. or d.c. with any voltage between 24 V
0 t
and 240 V. (See page opposite for use of timer in conjunction
Supply c or a
with other Telemecanique products).
RE1-LC Off-delay
The timer is connected in series with the load which
A1 L A1 A2
requires delayed de-energisation. Switch K is linked to
(1) (2)
0 t terminals Y2 and A2 of the timer and terminal A2 is linked
to the mains supply as shown in the scheme opposite. The
K
unit operates on a.c. current at a voltage between 24 V and
Supply c
240 V. (See page opposite for use of timer in conjunction
with other Telemecanique products).
Sequential diagrams
RE1-LA On-delay
Mains supply R must be switched on. When switch K
1
R
closes, the set timing period t starts and built-in indicator V
0
lights up simultaneously. When the set time period t has
1
elapsed, load C is energised and indicator V goes out. Load
K
0
C remains energised until switch K opens or until the mains
supply R is switched off.
1
C
0
V
t
RE1-LC Off-delay
Mains supply R must be switched on. When switch K
1
R
closes, load C is energised. When switch K opens, timing
0
starts and built-in indicator V lights up simultaneously.
1
When set time t has elapsed, load C is de-energised and
K
0
indicator V goes out. Load C then remains de-energised
until switch K closes again.
1
C
0
V
t
28411/4
Te
84
84
=
=
=
=
=
40
=
=
45
=
Y2
(3)
A2
(4)
RE 1 timing relays
Solid state output, width 17.5 mm
Characteristics :
page 28411/2
Compatibility with other Telemecanique products
References :
page 28411/3
Dimensions and schemes :
page 28411/4
The electronic timer can only operate correctly if the characteristics of the equipment with which it is associated are
compatible with the switching characteristics of the timer.
a.c. circuit 50 or 60 Hz
All RE1-LA and RE1-LC electronic timers are compatible with the Telemecanique a.c. controlled components listed
below :
Contactors for electricity supply authority dual tariffs, control relays, plug-in control relays
Type Operational Comments
voltage c
GY1-M 220 V 50 Hz 
CA2-K 24& 127 V 50/60 Hz for RE1-LA on 24 V : use a CA2-KNiiiZ7
24& 240 V 50/60 Hz for RE1-LC 
CA2-DN 24& 240 V 50/60 Hz on 24 V : use a CA2-DNiiZ7
CA2-DK 24& 240 V 50/60 Hz on 24 V : use a CA2-DKiiZ7
RHN, RHK 24& 127 V 50/60 Hz on 24 V : use an RHN, RHK-iiiJE
RE1-LA001 Mini-contactors and contactors
LC1-K 24& 127 V 50/60 Hz for RE1-LA on 24 V : use an LC1-KiiiiZ7
24& 240 V 50/60 Hz for RE1-LC 
LC1-D09 24& 240 V 50/60 Hz on 24 V : use an LC1-D09iiiZ7
LC1-D12 24& 240 V 50/60 Hz on 24 V : use an LC1-D12iiiZ7
LC1-D18 24& 240 V 50/60 Hz I0061/2 : use an LC1-D18iiiZ7
on 24 V
LC1-D25 24& 240 V 50/60 Hz on 24 V : use an LC1-D25iiiZ7
LC1-D32 24& 240 V 50/60 Hz on 24 V : use an LC1-D32iiiZ7
LC1-D40 to D95 110& 240 V 50/60 Hz 
Integral 18, 32 and 63 contactor breakers
LD1, LD5-LB 110& 240 V 50/60 Hz 
LD1, LD4, LD5-LC and LD 110& 240 V 50/60 Hz 
Contactors
Type Supply Coil Rectifier
voltage c
LC1-F115, F150, F185, F225, 220, 240 V 50/60 Hz LX1-FF, FG, FHiii2 
F265, F330 220 V 50/60 Hz LX9-FJ931 + DR5-TE4U
240 V 50/60 Hz LX9-FJ932 + DR5-TE4U
RE1-LC112 LC1-F500 220 V 50/60 Hz LX9-FK931 + DR5-TE4U
240 V 50/60 Hz LX9-FK932 + DR5-TE4U
LC1-F630 220 V 50/60 Hz LX9-FL930 + DR5-TE4U
240 V 50/60 Hz LX9-FL931 + DR5-TE4U
d.c. circuit
RE1-LA timers are compatible with the components listed below :
Mini-control relays, control relays and plug-in control relays
Type Supply Comments
voltage a
CA3-K 24& 72 V on 24 V : use a CA3-KNiiZD
CA3-DN 24& 240 V on 24 V : use a CA3-DNiiZD
CA3-DK 24& 240 V on 24 V : use a CA3-DKiiZD
CA4-DN 24 V Use a CA4-DNiiBW
RHN 24& 125 V on 24 V : use an RHN-iiiJV
RHK 24& 125 V on 24 V : use an RHK-iiiJV
RE1-LA301
Mini-contactors and contactors
LP1-K 24& 72 V on 24 V : use an LP1-KiiiiZD
LP4-K 24 V Use an LP4-KiiiiBW3
LP1-D09 to D32 24& 240 V on 24 V : use an LP1-DiiiiZD
LP1-D40 to D80 48& 240 V 
LP4-D12 24 V Use an LP4-D12iiBW
Contactors
Type Supply Coil
voltage a
LC1-F115, F150 220 V LX4-FF220
240 V LX4-FF250
LC1-F185, F225 220 V LX4-FG220
240 V LX4-FG250
LC1-F265, F330 220 V LX4-FH220
240 V LX4-FH250
Other combinations For other operational voltages and other contactors,
please consult your Regional Sales Office.
28411/5
Te
Zelio Time timing relays
Functions and selection
Functions
Diagram Operating principle
On-delay
Control or
Timing starts when the relay is energised. When the set time delay (t) has elapsed, the output contact closes. When the
supply
relay is de-energised, the contact returns to its initial position. The output contact does not close if the duration of the
C/O contact
control instruction is less than the set time delay.
t
Timing can also be started by opening of a control contact (models with external control).
Off-delay
Control or
Energisation of the relay or closing of the control contact (models with external control) causes the output relay to close
supply
instantaneously . Timing starts when the relay is de-energised or when the control contact opens. When the set time delay
C/O contact
(t) has elapsed, the contact returns to its initial position. If the energisation time or closing time of the control contact is
t
less than the minimum time specified, the timing period does not start.
On and Off-delay
Symmetrical
Control or
supply
This function is a combination of the The On and Off delays are equal.
On and Off delay functions. The timing
C/O contact
cycle must be controlled by an external Asymmetrical
ta tr
contact. The On and Off delays are adjusted by 2 different potentiometers.
Timing relay with pulse on energisation
Supply Energisation of the relay causes the output contact to close instantaneously and start the timing period. The contact
returns to its initial position when the set time delay (t) has elapsed or if the supply is cut off before the end of the timing
C/O contact
period.
t
Timing relay with pulse on de-energisation or on opening of a external control contact
Control or
supply De-energisation of the relay or opening of the external control contact (depending on model) causes the output contact
to close instantaneously and start the timing period. When the set time delay (t) has elapsed, the contact returns to its
C/O contact
initial position.
t
Flashing relay
Symmetrical flashing relay
Alimentation Energisation of the relay starts the The On and Off flashing phases are identical.
flashing period and causes the output
Contact  OF
relay to start the flashing cycle. When Asymmetrical flashing relay
ta tr
the relay is de-energised, the contact The On and Off flashing phases are adjusted by 2 different potentiometers
returns to its initial position. (ta and tr).
Time delay relays for star-delta starters
Alimentation Energisation of the relay causes the star contactor to close instantaneously and starts the timing period. When the set
time delay (t) has elapsed, the star contactor returns to its initial position and the delta contactor closes, after a breaking
Etoile
time sufficient for the changeover.
Triangle
t t3
Multifunction relays
On-delay - Pulse on energisation contact - Symmetrical flasher
Same functions as above +
Off-delay - Pulse on energisation contact with externally controlled start - Symmetrical flasher
Same functions as above +
Star Delta starting (External control of start of the timing period is not possible for the star delta starting function).
28460/2
Te
Additional functions
External control of starting: opening of an external contact connected to the relay starts the timing period. Closing of this contact resets the timer.
External control of partial stop of time delay: closing of an external contact connected to the relay allows the timing period to be interrupted. The time
elapsed is memorised. Timing restarts as soon as the contact opens. This type of control enables the totalising function to be performed.
External adjustment of the time delay: one or more external potentiometers can be used for remote adjustment of the timing period or periods.
Output Multifunction relay See pages
Solid state RE9-TA 28466/2
1 C/O RE7-TL or RE8-TA RE7: 28451/2, RE8: 28462/2
2 C/O RE7-TP 28451/2
1 C/O RE7-TM 28451/2
Solid state RE9-RA 28466/2
1 C/O RE7-RB11 or RE8-RB RE7: 28453/2, RE8: 28462/2
2 C/O RE7-RL 28453/2
2 C/O RE7-RB13 28453/2
1 C/O RE8-RA 28462/2
1 C/O RE7-RA and RE7-RM 28453/2
2 C/O RE7-MA13 28452/2
1 C/O RE7-MA11 28452/2
1 C/O RE7-MV 28452/2
1 C/O RE7-PE or RE8-PE RE7: 28454/2, RE8: 28463/2
2 C/O RE7-PP 28454/2
1 C/O RE8-PT 28463/2
2 C/O RE7-PD 28454/2
1 C/O RE7-PM 28454/2
1 C/O RE8-PD 28463/2
1 C/O RE7-CL or RE8-CL RE7: 28455/2, RE8: 28462/2
2 C/O RE7-CP 28455/2
1 C/O RE7-CV 28455/2
1 C/O RE8-YG 28463/2
2 C/O RE7-YA and RE7-YR 28456/2
1 N/C + N/O RE8-YA 28463/2
Output Multifunction relay See pages
Solid state RE9-MS 28467/2
1 C/O RE7-ML 28457/2
2 C/O RE7-MY13MW 28457/2
2 C/O RE7-MY13BU 28457/2
28460/3
Te
Zelio Time timing relays
References :
Solid state output, width 22.5 mm, optimum
pages 28466/2 and 28467/2
Dimensions :
page 28468/2
General characteristics
Schemes, setting-up :
pages 28466/3 and 28467/3
Compatibility :
page 28468/3
Presentation
The RE9 range of relays is designed for simple, repetitive applications with short and intensive cycles because their solid
state output provides very high electrical durability.
Each product has a single timing range.
Each relay has a wide voltage range from 24 to 240 V.
The range comprises 9 references with 3 model types:
- RE9-TA: On-delay,
- RE9-RA: Off-delay,
- RE9-MS: multifunction.
These products have a transparent, hinged flap on their front face to avoid any accidental alteration of the setting.
This flap can be directly sealed.
Environment
Conforming to standards IEC 61812-1, EN 61812-1
Product approvals CSA, GL pending, UL
Ł marking Zelio Time timing relays conform to European regulations
relating to Ł marking
Ambient air temperature Storage C - 40& + 85
around the device Operation C - 20& + 60
Permissible relative humidity range Conforming to IEC 60721-3-3 15& 85 % Environmental class 3K3
Vibration resistance Conforming to IEC 6068-2-6, 10 to 55 Hz a = 0.35 ms
Shock resistance Conforming to IEC 6068-2-27 15 gn - 11 ms
Degree of protection Casing IP 50
Terminals IP 20
Degree of pollution Conforming to IEC 60664-1 3
Overvoltage category Conforming to IEC 60664-1 III
Rated insulation voltage Conforming to IEC V 250
Conforming to CSA V 300
Test voltage for Dielectric test kV 2.5
insulation tests Shock wave kV 4.8
Voltage limits Power supply circuit 0.85& 1.1 Uc
Frequency limits Power supply circuit Hz 50/60 ą 5 %
Disconnection value Power supply circuit > 0.1 Uc
Mounting position In relation to normal vertical Any position
without derating mounting plane
Connection Flexible cable without cable end mm2 2 x 2.5
Maximum c.s.a. Flexible cable with cable end mm2 2 x 1.5
Tightening torque N.m 0.6& 1.1
Immunity to electromagnetic interference (EMC) (Application class 2 conforming to EN 61812-1)
Electrostatic discharge Conforming to IEC 61000-4-2 Level 3 (6 kV contact, 8 kV air)
Electromagnetic fields Conforming to IEC 61000-4-3 Level 3 (10 V/m)
Fast transients Conforming to IEC 61000-4-4 Level 3 (2 kV)
Shock waves Conforming to IEC 61000-4-5 Level 3 (2 kV)
Radiated and CISPR11 Group 1 class A
conducted emissions CISPR22 Class A
28465/2
Te
Zelio Time timing relays
References :
Solid state output, width 22.5 mm, optimum
pages 28466/2 and 28467/2
Dimensions :
page 28468/2 General characteristics (continued)
Schemes, setting-up :
pages 28466/3 and 28467/3
Compatibility :
page 28468/3
Type of timing relay RE9-TA RE9-RA RE9-MS
On-delay Off-delay Multifunction
Power supply characteristics
Supply voltage V z 24& 240 c 24& 240 z 24& 240. See page
28467/2
Voltage limits Power supply circuit 0.85& 1.1 Un
Frequency Hz 50& 60 ą 5 %
Control contact Mechanical only In series Between Y2 and A2 In series
Maximum length of connecting cable From contact to RE9 m  20 
Control input consumption Input Y2 mA  5 
Time delay characteristics
Setting accuracy < ą 20 %
Repeat accuracy < 1 %
Minimum reset time After the time delay period ms 100
Minimum switching time ms  40 
Maximum immunity During the time delay period ms 100 2 70
to micro-breaks
After the time delay period ms 2 2
Temperature drift d" 0.1 % per degree centigrade
Switching characteristics (solid state type)
Maximum continuous current At ambient temperature: 20 C A 0.7 (minimum 10 mA)
Maximum overload current VDE 0435 part. 303, 4.8.3/Class II A 15 for 10 ms
Maximum voltage drop Closed state V A 0.7 A : 3
Leakage current Open state mA d" 6 d" 1 d" 6
Maximum dissipated power W 2.5 4 2.5
Derating For temperature > 20 C mA None
Electrical durability In millions of operating > 100
cycles
(1) RE9-MS at 60 C maximum current: up to 48 V: 400 mA, from 48 V to 240 V: 300 mA.
28465/ 3
Te
Zelio Time timing relays
Characteristics :
Solid state, width 22.5 mm, optimum
pages 28465/2 and 28465/3
Dimensions :
page 28468/2 Functions, references
Schemes, setting-up :
page 28466/3
Compatibility :
page 28468/3
On-delay relays
Supply
Control
contact K
de-energised
Load
energised
t
open
closed
t: adjustable On-delay
Power supply Function Timing Reference Weight
circuit range (1) kg
a.c. On-delay 0.1 s& 10 s RE9-TA11MW 0.110
or
d.c.
24& 240 V
0.3 s& 30 s RE9-TA31MW 0.110
3 s& 300 s RE9-TA21MW 0.110
RE9-TA
40 s& 60 min RE9-TA51MW 0.110
Off-delay relays
Supply
Control
contact K
de-energised
Load
energised
t
open
closed
t: adjustable Off-delay
Power supply Function Timing Reference Weight
circuit range (1) kg
a.c. Off-delay 0.1 s& 10 s RE9-RA11MW7 0.110
24& 240 V
0.3 s& 30 s RE9-RA31MW7 0.110
3 s& 300 s RE9-RA21MW7 0.110
40 s& 60 min RE9-RA51MW7 0.110
(1) For easier adjustment, it is preferable to set the time delay between the maximum value in the range and one tenth
of this value.
Example: RE9-TA11MW timing range 0.1 s& 10 s, recommended use 1 s& 10 s.
28466/ 2
Te
Zelio Time timing relays
Characteristics :
Solid state output, width 22.5 mm, optimum
pages 28465/2 and 28465/3
On-delay, Off-delay relays
References :
page 28466/2
Dimensions :
Schemes, setting-up
page 28468/2
Compatibility :
page 28468/3
Schemes
Terminal blocks
RE9-TA RE9-RA
A1 L A1 L
Y2 A2
Recommended application schemes
RE9-TA
RE9-TA
Load
K The timing relay is placed in series with the load whose energisation is to be delayed on one side, and switch
A1 L
K on the other side. The mains supply may be a.c. or d.c. and the voltage may be between 24 V and 240 V.
See function diagram on page opposite.
Supply c or a
RE9-RA
RE9-RA
Load
The timing relay is placed in series with the load whose de-energisation is to be delayed. Switch K is
A1 L
connected to terminals Y2 and A2 of the timing relay, and terminal A2 is connected to the mains supply as
indicated in the scheme opposite. The device is operated from an a.c. mains supply whose voltage is between
Y2 A2
K
24 V and 240 V. See function diagram opposite.
Supply c
Note: For supply voltages greater than 30 V, the rated voltage of the load is equal to the supply voltage. For a supply voltage of 24 V, the voltage drop within the
RE9 relay must be taken into account (about 3 V); a coil with a nominal voltage of 21 V must therefore be selected for the load (see page 28468/3).
Setting-up
1 Potentiometer for fine adjustment of the time delay, graduated in % of the range 1, see below.
2 Marking of maximum time delay value.
1
3 LED :
- Yellow LED: flashes during the time delay period; permanently on outside the time delay period.
2
3
Adjustment of the time delay
- The maximum value of the timing range is printed on the product, 2.
1 24
Example: RE9-TA11MW; maximum time delay: 10 s.
- Time required 2.4 s; using potentiometer 1 set the value of the time delay required as a % of value 2:
2 10 s x. %
t x 100 2.4 x 100
value 1 =       =         = 24
2 10
Time set = 2.4 s
28466/3
Te
Zelio Time timing relays
Characteristics :
Solid state output, width 22.5 mm, optimum
pages 28465/2 and 28465/3
Multifunction timing relays
Dimensions :
page 28468/2
Schemes, setting-up :
Functions, references
page 28467/3
Compatibility :
page 28468/3
1
Multifunction timing relays, , ,
1
On-delay Pulse on energisation
Supply Supply
Control Control
contact K contact K
Load Load
t t
Flashing, start Flashing, start
on energisation of the load on de-energisation of the load
Supply Supply
Control Control
de-energised
contact K contact K
energised
open
Load Load
closed
= = = =
t: time delay
t t t t
Power supply Functions Timing Reference Weight
circuit range (1) kg
a.c. On-delay 3 s& 300 s RE9-MS21MW 0.075
or and
d.c. 0.1 s& 10 s
24& 240 V
a.c. Pulse on energisation
24& 240 V
1
RE9-MS
a.c. Flashing.
24& 240 V Start on
energisation
of the load.
a.c. Flashing.
24& 240 V Start on
de-energisation
of the load.
(1) For easier adjustment, it is preferable to set the time delay between the maximum value in the range and one tenth
of this value.
Example: RE9-MS21MW timing range 3 s& 300 s, recommended use 30 s& 300 s.
28467/ 2
Te
Zelio Time timing relays
Characteristics :
Solid state output, width 22.5 mm, optimum
pages 28465/2 and 28465/3
Multifunction timing relays
References :
page 28467/2
Dimensions :
Schemes, setting-up
page 28468/2
Compatibility :
page 28468/3
Schemes
Terminal block
RE9-MS
A1 X4 L
X1 X2 X3
Recommended application schemes
RE9-MS
1
On-delay Pulse on energisation Selection of timing range
X3-X4 not linked: range 3 s& 300 s
(factory configuration)
X3 X4 X1 X3 X4
Load Load
K K
A1 L A1 A2 A1 L A1 A2
X3-X4 linked: range 0.1 s& 10 s
RE9-MS RE9-MS
Supply c
Supply c or a
Link to be made between terminals X1 and X4.
Flashing Flashing
Start on energisation of the load Start on de-energisation of the load
X1 X2 X3 X4 X2 X3 X4
Load Load
K K
A1 L A1 A2 A1 L A1 A2
RE9-MS RE9-MS
Supply c Supply c
Link to be made between terminals X2 and X4 Link to be made between terminals X2 and X4.
on one side and X1 and X2 on the other side.
Note: For supply voltages greater than 30 V, the rated voltage of the load is equal to the supply voltage. For a supply voltage of 24 V, the voltage drop within the
RE9 relay must be taken into account (about 3 V); a coil with a nominal voltage of 21 V must therefore be selected for the load (see page 28468/3).
Setting-up
1 Potentiometer for fine adjustment of the time delay, graduated in % of the range 1, see below.
2 Marking of maximum time delay value.
1
3 LED :
2
3
- Yellow LED: flashes during the time delay period; permanently on outside the time delay period.
Adjustment of the time delay
- The maximum value of the timing range is printed on the product, 2.
1 24
Example: RE9-MS21MW; maximum time delay: 10 s (X3-X4 linked).
- Time required 2.4 s; using potentiometer 1 set the value of the time delay required as a % of value 2:
2 10 s x. %
t x 100 2.4 x 100
value 1 =       =         = 24
time set = 2.4 s
2 10
28467/3
Te
Zelio Time timing relays
Characteristics :
Solid state output, width 22.5 mm, optimum
pages 28465/2 and 28465/3
References :
pages 28466/2 and 28467/2
Dimensions, mounting
Schemes, setting-up:
pages 28466/3 and 28467/3
Compatibility:
page 28468/3
RE9
Dimensions
80 22,5
Rail mounting
89,5
82
Screw fixing
4
28468/2
Te
78
6
78
6
Zelio Time timing relays
Characteristics : Solid state output, width 22.5 mm, optimum
pages 28465/2 and 28465/3
References :
Compatibility with other Telemecanique products
pages 28466/2 and 28467/2
Dimensions :
page 28468/2
Schemes, setting-up :
pages 28466/3 and 28467/3
Correct operation of electronic timing relays is only ensured when the characteristics of the equipment with which they
are associated are compatible with the switching characteristics of the relay.
a.c. circuit, 50 or 60 Hz
RE9-TA, RE9-RA and RE9-MS timing relays are compatible with the products listed below:
Plug-in control relays, control relays
Type Operational voltage c Comments
RHN, RHK 24& 110 V 50/60 Hz On 24 V: use an RHN, RHKiiiJV
RXN 48& 110 V 50/60 Hz for RE9-TA, RA 
48 V 50/60 Hz for RE9-MS 
RUN 48& 110 V 50/60 Hz 
CA2-K 24& 127 V 50/60 Hz for RE9-TA/MS On 24 V: use a CA2-KiiiZ7
24& 240 V 50/60 Hz for RE9-RA On 24 V: use a CA2-KiiiZ7
CA2-DN/DK 24& 240 V 50/60 Hz On 24 V: use a CA2-DNiiiZ7
Mini-contactors and contactors
LC1-K 24& 127 V 50/60 Hz for RE9-TA, MS On 24 V: use an LC1-KiiiZ7
24& 240 V 50/60 Hz for RE9-RA On 24 V: use an LC1-KiiiZ7
LC1-D09 to D38 24& 240 V 50/60 Hz On 24 V: use an LC1-D09iiiZ7
LC1-D40 to LC1-D95 110& 240 V 50/60 Hz 
Contactors
Type Operational voltage c Coil Rectifier
LC1-F115, LC1-F150 220/230 V, 240 V 50/60 Hz LX1-FFiii
LC1-F185, LC1-F225 220/230 V, 240 V 50/60 Hz LX1-FGiii
LC1-F265, LC1-F330 220/230 V, 240 V 50/60 Hz LX1-FHiii2
LC1-F400, F500, F630 220/230 V 50/60 Hz LX9-FJ/FK/FL931 + DR5-TE4U
240 V 50/60 Hz LX9-FJ/FK/FL932 + DR5-TE4U
integral 18, 32, 63 contactor breakers
Type Operational voltage c Comments
LD1-LB, LD5-LB 110& 240 V 50/60 Hz 
LD1-LC/LD, LD4-LC/LD.
LD5-LC/LD 110& 240 V 50/60 Hz 
d.c. circuit
RE6-TA and MS timing relays set to on-delay function are compatible with the products listed below:
Plug-in control relays, control relays and mini-control relays
Type Operational voltage a Comments
RE9-TA RE9-MS
RHN, RHK 24& 125 V 24& 48 V On 24 V: use an RHN, RHKiiiJV
RXN 48 V  
RUN 48 V 48 V 
CA3-K 24& 240 V 24& 72 V On 24 V: use a CA3-KiiiZD
CA4-K 24& 72 V 24& 48 V On 24 V: use a CA4-KiiiBW3
CA3-DN/DK 24& 240 V 24& 240 V On 24 V: use a CA3-DiiiiZD
CA4-DN 24& 72 V 24& 48 V On 24 V: use a CA4-DNiiiBW
Mini-contactors and contactors
LP1-K 24& 220 V 24& 72 V On 24 V: use an LP1-KiiiZD
LP4-K 24& 72 V 24& 48 V 
LP4-D12 to LP4-D25 24& 72 V 24& 48 V On 24 V: use an LP4-DiiiBW
LP1-D09 to LP1-D38 24& 240 V 24& 240 V On 24 V: use an LP1-DiiiiiZD
LP1-D40 to LP1-D80 48& 240 V 48& 240 V 
Contactors
Type Operational voltage a Comments
LC1-F115 to LC1-F330 220/230 V LX4-FF/FG/FH220
240 V LX4-FF/FG/FH250
28468/3
Te
Zelio Time timing relays
References : Relay output, width 22.5 mm, universal
pages 28451/2 to 28457/2
Dimensions :
General characteristics
page 28458/2
Schemes :
pages 28451/3 to 28458/2
Setting-up :
pages 28451/3 to 28458/3
Presentation
The RE7 range of relays, with only 23 references, covers all timing applications.
These relays offer multi-range timing from 50 ms to 300 h.
They are multi-voltage.
Three models combine several different functions: multifunction relays.
These products have a transparent, hinged flap on their front face to avoid any
accidental alteration of the settings. This flap can be directly sealed.
Environment
Conforming to standards IEC 61812-1, EN 61812-1
Product approvals CSA, GL pending, UL
Ł marking Zelio Time timing relays conform to European
regulations relating to Ł marking
Ambient air temperature Storage C - 40& + 85
around the device Operation C - 20& + 60
Permissible relative humidity range Conforming to IEC 60721-3-3 15& 85 % Environmental class 3K3
Vibration resistance Conforming to IEC 6068-2-6, 10 to 55 Hz a = 0.35 ms
Shock resistance Conforming to IEC 6068-2-27 15 gn - 11 ms
Degree of protection Casing IP 50
Terminals IP 20
Degree of pollution Conforming to IEC 60664-1 3
Overvoltage category Conforming to IEC 60664-1 III
Rated insulation voltage Conforming to IEC V 250
Between contact circuit and power
supply or between contact circuit Conforming to CSA V 300
and control inputs
Test voltage for insulation tests Dielectric test kV 2.5
Shock wave kV 4.8
Voltage limits Power supply circuit 0.85& 1.1 Uc
Frequency limits Power supply circuit Hz 50/60 ą 5 %
Disconnection value Power supply circuit > 0.1 Uc
Mounting position In relation to normal Any position
without derating vertical mounting plane
Connection Maximum c.s.a. Flexible cable without cable end mm2 2 x 2.5
Flexible cable with cable end mm2 2 x 1.5
Tightening torque N.m 0.6& 1.1
Immunity to electromagnetic interference (EMC) (Application class 2 conforming to EN 61812-1)
Electrostatic discharge Conforming to IEC 61000-4-2 Level 3 (6 kV contact, 8 kV air)
Electromagnetic fields Conforming to IEC 61000-4-3 Level 3 (10 V/m)
Fast transients Conforming to IEC 61000-4-4 Level 3 (2 kV)
Shock waves Conforming to IEC 61000-4-5 Level 3 (2 kV)
Radiated and CISPR11 Group 1 class A
conducted emissions CISPR22 Class A
Consumption
c 50/60 Hz a
Average consumption 24 V 48 V 110 V 240 V 24 V 48 V 110 V 240 V
RE7-ii11BU VA 0.7 1.6 1.8 8.5 W 0.5 1.2  
RE7-ii12BU and RE7-ii13BU VA 1.2 2 2.8 12.5 W 0.8 1.6  
RE7-iiiiMW (1) VA 2 2.5 3.2 6 W 2 1 3.2 2
(1) RE7-RBiiMW: current peak on energisation = 1 A / 30 ms.
28450/2
Te
Zelio Time timing relays
References : Relay output, width 22.5 mm, universal
pages 28451/2 to 28457/2
Dimensions :
General characteristics (continued)
page 28458/2
Schemes :
pages 28451/3 to 28458/2
Setting-up :
pages 28451/3 to 28458/3
Time delay characteristics
Setting accuracy As % of the full scale value ą 10 %
Repeat accuracy ą 0.2 %
Influence of voltage In the voltage range, 0.85& 1.1 Un < 0.2 %
Influence of temperature < 0.07 %/C
Immunity to micro-breaks ms 3
Minimum control pulse ms 20 (except RE7-RB1iMW: 1 s)
Reset time ms 50
Output circuit characteristics
Maximum switching voltage V z 250
Mechanical durability In millions of operating cycles 20
Current limit Ith A 8 (except RE7-RBiiMW: 5 A)
Rated operational limits at 70 C 24 V 115 V 250 V
Conforming to IEC 60947-5-1/1991 AC-15 A 333
and VDE 0660 DC-13 A 2 0.2 0.1
Minimum switching capacity 12 V/10 mA
Contact material Nickel Silver 90/10
(except RE7-RBiiMU: gold flashed silver alloy)
Remote control input characteristics
Maximum voltage Applicable to inputs V 60
Y1Z2, X1Z2, X2Z2
Signal delivered by Y1Z2, Switching current mA < 1
X1Z2, X2Z2 control inputs Maximum distance m 50
No galvanic insulation between Compatibility 3/4-wire PNP and NPN Telemecanique sensors or
these inputs and the supply other sensors without an internal load
Potentiometer for connection Type Linear at ą 20 %
between terminals Z1Z2, Z3Z2 Resistance k&! 47 ą 20 %
Power W 0.2
Maximum distance m 25 by shielded cable: shielding linked to terminal Z2
a.c. load d.c. load
Curve 1 Curve 2 Load limit curve
Electrical durability of contacts on resistive Reduction factor k for inductive loads
load in millions of operating cycles (applies to values taken from the
durability curve opposite)
1 300
10
0,9
200
0,8
0,7
100
3
1
0,6
2
50
0,5
40
1
0,1 30
0,4
20
A
A
0,3 10
0,01
1 0,8 0,6 0,5 0,4 0,3 0,2 0,1 0,2 0,5 1 2 5 10 20
0 1 2 3 4 5 6 7 8
Current broken in A Power factor on breaking (cos ) Current in A
A RE7-RBiiMW A RE7-RBiiMW
1 L/R = 20 ms
Example: 2 L/R with load protection diode
3 Resistive load
An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current
+
consumption equal to 0.1 A and cos  = 0.3
RE7
For 0.1 A, curve 1 indicates a durability of approximately 1.5 million operating cycles.
As the load is inductive, it is necessary to apply a reduction coefficient k to this number of
cycles, as indicated by curve 2.
K
For cos  = 0.3: k = 0.6 
The electrical durability therefore becomes:
1.5 106 operating cycles x 0.6 = 900 000 operating cycles
28450/3
Te
Voltage in V
Reduction factor k
Millions of operating cycles
Zelio Time timing relays
Relay output, width 22.5 mm, universal
On-delay relays
Functions, references
On-delay relays
Time delay adjustable from 0.05 s to 300 h in 10 ranges (see setting-up procedure on page opposite).
On-delay relay External control for External control for partial
Start on start of time delay stop of time delay
energisation RE7-TM (for totalising function)
RE7-TL, TM, TP RE7-TM
de-energised
Supply Supply
Supply
energised
open 15/18 (25/28) (Y1Z2) (X1Z2)
Start Partial stop
C/O
15/16 (25/26)
closed
t1 t3
t2
t
t: adjustable On-delay 15/18
C/O
15/16
C/O 15/18
t
15/16
t t=t1+t2 + t3
Conversion of second changeover contact to instantaneous mode by means of switch R2
RE7-TP13BU
R2 R2
Delay Inst Delay Inst
Supply Supply
C/O 25/28 21/24
C/O
25/26 21/22
t
Functions (see Supply Relay Reference Weight
diagrams above) voltages output kg
On-delay relay a or c 24 V 1 C/O RE7-TL11BU 0.150
c 110& 240 V
On-delay relay a or c 24 V 1 C/O RE7-TM11BU 0.150
External control possible for: a or c 42& 48 V
- start of time delay c 110& 240 V
RE7- T
- partial stop of time delay
- adjustment of time delay (1)
On-delay relay a or c 24 V 2 C/O (2) RE7-TP13BU 0.150
Remote control possible for: a or c 42& 48 V
- adjustment of time delay (1) c 110& 240 V
(1) By external potentiometer, to be ordered separately. If external potentiometer is fitted, the internal potentiometer is
automatically disconnected.
(2) A switch on the front face of the relay allows the second changeover contact to be used in instantaneous mode.
28451/2
Te
Zelio Time timing relays
Relay output, width 22.5 mm, universal
On-delay relays
Schemes, setting-up
Schemes
Terminal blocks
RE7-TL11BU RE7-TP13BU RE7-TM11BU
A1 15 B1 A1 15 B1 A1 15 B1
Z1 25 (21) B2 Z1 B2
28 (24) 26 (22) Z2 X1 Y1 Z2
18 16 A2 18 16 A2 18 16 A2
Recommended application schemes
Start on energisation Start by external contact External control of partial stop
B1 B2 A1
B1 B2 A1 Y1 B1 B2 A1
X1
Z2 Z2
A2 A2
A2
Potentiometer wiring Wiring precautions
Z1
X1 or Y1 or Z1
Z2
A2
Z2
A2
No galvanic insulation between supply terminals A1, A2, B1, B2 and control inputs X1, Y1, Z1, Z2.
Setting-up
1 Potentiometer for fine adjustment of the time delay, graduated in % of range max. setting 2.
2 10-position timing range selector:
1
0.05& 1 s 0.5& 10 s 5& 100 s 1.5& 30 min 1.5& 30 h
4
0.15& 3 s 1.5& 30 s 15& 300 s 15& 300 min 15& 300 h
2
3 Switch for converting the second C/O contact to instantaneous mode (for RE7-TP13BU).
3
4 LEDs, depending on the model:
- Green LED U/T: flashes during the time delay period, permanently on outside the time delay period.
- Yellow LED R1: on when the 1st relay is energised.
- Yellow LED R2: on when the 2nd relay is energised.
Adjustment of the time delay
1 40
- Select the timing range immediately greater than the time required, using selector switch 2.
Example: time required 12 s; range selected 30 s.
2 30 s x. %
- Using potentiometer 1 display the required time value as a % of value 2.
t x 100 12 x 100
1 =       i.e.        = 40
2 30
28451/3
Te
B1
A1
B1
A1
B1
A1
18
15
28
25
16
26
A2
B2
16
18
15
16
18
15
A2
A2
B2
(24)
(21)
(22)
c
110 & 240 V
z 42& 48 V
z 24 V
c
110 & 240 V
z 42& 48 V
z 24 V
c
110 & 240 V
z 42 & 48 V
z 24 V
Supply
Zelio Time timing relays
Characteristics :
Relay output, width 22.5 mm, universal
pages 28450/2 and 28450/3
On-delay and Off-delay relays
Dimensions :
page 28458/2
Schemes :
Functions, references
page 28458/2
Setting-up :
page 28458/3
On-delay and Off-delay relays ,
Time delay adjustable from 0.05 s to 300 h in 10 ranges (see setting-up procedure on page opposite).
External control for Remote control for partial stop of time delay
start of time delay RE7-MA11BU and MV11BU
RE7-MA and MV
Y1Z2
de-energised Supply Start
energised
Y1Z2
open Start C/O 15/18
15/16
closed
ta : adjustable On-delay C/O 15/18 (25/28)
15/16 (25/26) Partial stop
X1Z2
tr: adjustable Off-delay
of time delay
ta tr
ta = t1 + t2
t1 ts t2 t3 ts t4
tr = t3 + t4
ts: partial stop time
Conversion of second changeover contact to instantaneous mode by means of switch R2
RE7-MA13BU
R2 R2
Delay Inst Delay Inst
Supply Supply
Start C/O 21/24
21/22
C/O 25/28
25/26
ta tr
Functions Supply Relay Reference Weight
(see diagrams above) voltages output kg
Symmetrical relays: On and Off delay times are equal.
On-delay and Off-delay relay a or c 24 V 1 C/O RE7-MA11BU 0.150
External control possible for a or c 42& 48 V
- partial stop of time delay c 110& 240 V
- adjustment of time delay (1)
Start control via
external contact only
On-delay and Off-delay relay a or c 24 V 2 C/O (2) RE7-MA13BU 0.150
RE7-M
Start control via a or c 42& 48 V
external contact only c 110& 240 V
Asymmetrical relays: On and Off delay times are adjusted separately.
On-delay and Off-delay relay a or c 24 V 1 C/O RE7-MV11BU 0.150
External control possible for a or c 42& 48 V
- partial stop of time delay c 110& 240 V
- adjustment of time delays (1)
Start control via
external contact only
(1) By external potentiometer(s), to be ordered separately. If external potentiometer(s) is/are fitted, the internal
potentiometer(s) is/are automatically disconnected.
(2) A switch on the front face of the relay allows the second changeover contact to be used in instantaneous mode.
28452/2
Te
Zelio Time timing relays
Relay output, width 22.5 mm, universal
On-delay and Off-delay relays
Characteristics :
pages 28450/2 and 28450/3
References :
Schemes, setting-up
page 28452/2
Dimensions :
page 28458/2
Schemes
Terminal blocks
RE7-MA13BU RE7-MA11BU RE7-MV11BU
A1 15 B1 A1 15 B1
A1 15 B1
Z1 B2 Z1 Z3 B2
Y1 25 (21) B2
X1 Y1 Z2 X1 Y1 Z2
28 (24) 26 (22) Z2
18 16 A2 18 16 A2
18 16 A2
Recommended application schemes (for other schemes, see page 28458/2)
Start by external control External control of partial stop
B1 B2 A1 B1 B2 A1
Y1 X1
Z2 Z2
A2 A2
Potentiometer wiring Potentiometer wiring Wiring precautions
for symmetrical relay for asymmetrical relays
RE7-MA RE7-MV11BU
Z3
Z1
Z1
X1 or Y1 or Z1
Z2
A2
Z2
A2
Z2
(1) (2) A2
No galvanic insulation between supply terminals A1, A2, B1, B2 and control inputs X1, Y1, Z1, Z2.
(1) On-delay adjustment
(2) Off-delay adjustment
Setting-up procedure
Symmetrical Asymmetrical
timing relay timing relay
1 Potentiometer for fine adjustment of the time delay, graduated in % of range max. setting 2
2 10-position timing range selector :
1 4
0.05& 1 s 0.5& 10 s 5& 100 s 1.5& 30 min 1.5& 30 h
1
4
A
]
0.15& 3 s 1.5& 30 s 15& 300 s 15& 300 min 15& 300 h
2
2
1
B A On-delay adjustment (ta).
]
2
3
B Off-delay adjustment (tr).
3 Switch for converting the second changeover contct to instantaneous mode (RE7-MA13BU).
4 LEDs, depending on the model :
- Green LED: flashes during the time delay period, permanently on outside the time delay period
- Yellow LED 1: on when the 1st relay is energised
- Yellow LED 2: on when the 2nd relay is energised
Adjustment of the time delay
1 40
- Select the timing range value immediately greater than the time required using selector switch 2.
Example: required time 12 s; range selected 30 s.
2 30 s x. %
- Using potentiometer 1 display the required time as a % of value 2.
t x 100 12 x 100
1 =       i.e.        = 40
2 30
28452/3
Te
B1
A1
B1
A1
B1
A1
18
15
16
A2
B2
16
18
15
A2
B2
18
15
28
25
16
26
A2
B2
(24)
(21)
(22)
c
110 & 240 V
z 42& 48 V
z 24 V
c
110 & 240 V
z 42& 48 V
z 24 V
Supply
Zelio Time timing relays
Relay output, width 22.5 mm, universal
Off-delay relays
Functions, references
Off-delay relays
Off-delay relays External control for Remote control for
RE7-RB start of time delay partial stop of time delay
RE7-RA, RM RE7-RA, RM
> 1 s (1) > 20 ms
de-energised Supply Supply Start Y1Z2
energised
C/O
open 15/18 (25/28) Start Partial stop X1Z2
15/16 (25/26)
closed
t
C/O 15/18 C/O
t: adjustable Off-delay 15/18
15/16
15/16
t = t1 + t2
t t1 ts t2
t : partial stop time
Conversion of second changeover contact to instantaneous mode by means of switch R2
RE7-RL13BU
R2 R2
Delay Inst Delay Inst
Supply Supply
Start C/O 21/24
21/22
C/O 25/28
25/26
tr
Functions Supply Relay Reference Weight
(see diagrams above) voltages output kg
On de-energisation, adjustable from 0.05 s to 10 min in 7 ranges (see setting-up procedure on page opposite).
Off-delay relay a or c 24& 240 V 1 C/O RE7-RB11MW (1) 0.150
Off-delay relay a or c 24& 240 V 2 C/O RE7-RB13MW (1) 0.150
Remote control possible for:
- adjustment of time delay (2)
RE7-R
On opening of external control contact, adjustable from 0.05 s to 300 h in 10 ranges (see setting-up procedure on
page opposite).
Off-delay relay a or c 24 V 1 C/O RE7-RA11BU 0.150
External control possible for: a or c 42& 48 V
- partial stop of time delay c 110& 240 V
- adjustment of time delay (2)
On opening of low level external control contact, adjustable from 0.05 s to 300 h in 10 ranges (see setting-up
procedure on page opposite).
Off-delay relay a or c 24 V 1 C/O RE7-RM11BU 0.150
External control possible for: a or c 42& 48 V
- partial stop of time delay c 110& 240 V
- adjustment of time delay (2)
Off-delay relay a or c 24 V 2 C/O (3) RE7-RL13BU 0.150
a or c 42& 48 V
c 110& 240 V
(1) If the device has been stored, de-energised, for more than a month, it must be energised for about 15 seconds to
activate it. Subsequently, a time of > 1 s is enough to activate the time delay.
If this time is not complied with, the relay will remain energised indefinitely.
(2) By external potentiometer, to be ordered separately. If external potentiometer is fitted, the internal potentiometer is
automatically disconnected.
(3) A switch on the front face of the relay allows the second changeover contact to be used in instantaneous mode.
28453/2
Te
Zelio Time timing relays
Relay output, width 22.5 mm, universal
Off-delay relays
Schemes, setting-up
Schemes
Terminal blocks
RE7-RL13BU RE7-RB11MW RE7-RB13MW RE7-RM11BU and RE7-RA11BU
A1 15 B1
A1 15 B1 A1 15 A1 15
Z1 B2
Y1 25 (21) B2 Z1 25
X1 Y1 Z2
28 (24) 26 (22) Z2 28 26 Z2
18 16 A2
18 16 A2 18 16 A2 18 16 A2
Recommended application schemes
Start on de-energisation Start by low level Remote control Potentiometer wiring
external control of partial stop
RE7-RB RE7-RM and RL RE7-RA and RM
Z1
B1 B2 A1 B1 B2 A1
A1 Y1 X1
Z2
A2
Z2 Z2
A2 A2
A2
Start by external control Wiring precautions
RE7-RA RE7-RM and RL
+ +
A1 B2 B1
Y1 Y1 Y1
Z2
A2 A2 A2 A2
 
No galvanic insulation between supply terminals A1, A2, B1, B2 and control inputs X1, Y1, Z1, Z2.
Setting-up procedure
1 Potentiometer for fine adjustment of the time delay, graduated in % of range max. setting 2.
2 Timing range selector:
1
- 10-position (RE7-RA, RM, RL) 0.05& 1 s 0.5& 10 s 5& 100 s 1.5& 30 min 1.5& 30 h
4
0.15& 3.s 1.5& 30 s 15& 300 s 15& 300 min 15& 300 h
2 - 7-position (RE7-RB) 0.05& 1 s 0.5& 10 s 5& 100 s 1.5& 10 min
0.15& 3.s 1.5& 30 s 15& 300 s
3
3 Switch for converting the second changeover contact to instantaneous mode (RE7-RL13BU).
4 LEDs, depending on the model:
- Green LED U/T: flashes during the time delay period, permanently on outside the time delay period.
- Yellow LED R1: on when 1st relay is energised.
- Yellow LED R2: on when 2nd relay is energised.
- RE7-RBiiMW: the green LED does not flash during the time delay period and there is only one yellow
LED (R).
1 40
Adjustment of the time delay
- Select the timing range immediately greater than the time required, using selector switch 2.
2 30 s x. %
Example: required time 12 s; range selected 30 s.
- Using potentiometer 1 display the required time value as a % of value 2.
t x 100 12 x 100
1 =       i.e.        = 40
2 30
28453/3
Te
B1
A1
B1
A1
18
15
16
A2
B2
18
15
28
25
16
26
A2
A1
16
18
15
26
28
25
A2
B2
16
18
15
A2
A1
(24)
(21)
(22)
z 24 & 240 V
c
110 & 240 V
z 42& 48 V
z 24 V
c
110 & 240 V
z 42& 48 V
z 24 V
Supply
a 24 V
c 24 V
a 42& 48 V
c 42& 48 V
c
110 & 240 V
Zelio Time timing relays
Characteristics :
Relay output, width 22.5 mm, universal
pages 28450/2 and 28450/3
Pulse on energisation relays
Dimensions :
page 28458/2
Schemes :
Functions, references
page 28458/2
Setting-up :
page 28458/3
Pulse on energisation relays
Time delay adjustable from 0.05 s to 300 h in 10 ranges (see setting-up procedure on page opposite)
Pulse on energisation relay Start on opening of External control for
Start on energisation external control contact partial stop of time delay
RE7-PE, PP RE7-PM, PD (for totalising function)
RE7-PM
de-energised Supply Supply Supply
energised
15/18 (25/28)
open C/O Start Y1Z2 Partial stop X1Z2
15/16 (25/26)
closed
t1 t2 t3
t
C/O C/O
t: pulse time 15/18
15/16
ts: partial stop time
t
15/18
15/16
t = t1 + t2 + t3 t
Conversion of second changeover contact to instantaneous mode by means of switch R2
RE7-PP
R2 R2
Delay Inst Delay Inst
Supply Supply
C/O 25/28 C/O 21/24
25/26 21/22
t
RE7-PD
R2 R2
Delay Inst Delay Inst
Supply Supply
Start Y1Z2
C/O 21/24
21/22
C/O
25/28
25/26
t
Functions Supply Relay Reference Weight
(see diagrams above) voltages output kg
1
Start on energisation
Pulse on energisation relay a or c 24 V 1 C/O RE7-PE11BU 0.150
c 110& 240 V
Pulse on energisation relay a or c 24 V 2 C/O (1) RE7-PP13BU 0.150
External control possible for a or c 42& 48 V
- adjustment of time delay (2) c 110 & 240 V
RE7-P
1
Start on opening of external control contact
Pulse on energisation relay a or c 24 V 1 C/O RE7-PM11BU 0.150
External control possible for a or c 42& 48 V
- partial stop of time delay c 110& 240 V
- adjustment of time delay (2)
Pulse on energisation relays a or c 24 V 2 C/O (1) RE7-PD13BU 0.150
a or c 42& 48 V
c 110& 240 V
(1) A switch on the front face of the relay allows the second changeover contact to be used in instantaneous mode.
(2) By external potentiometer, to be ordered separately. If external potentiometer is fitted, the internal potentiometer is
automatically disconnected.
28454/2
Te
Zelio Time timing relays
Relay output, width 22.5 mm, universal
Pulse on energisation relays
Characteristics :
pages 28450/2 and 28450/3
References :
Schemes, setting-up
page 28454/2
Dimensions :
page 28458/2
Schemes
Terminal blocks
RE7-PE11BU RE7-PP13BU RE7-PD13BU RE7-PM11BU
A1 15 B1
A1 15 B1 A1 15 B1 A1 15 B1
Z1 B2
Z1 25 (21) B2 Y1 25 (21) B2
X1 Y1 Z2
28 (24) 26 (22) Z2 28 (24) 26 (22) Z2
18 16 A2
18 16 A2 18 16 A2 18 16 A2
Recommended application schemes (for other schemes, see page 28458/2)
Start on energisation Start by external contact External control of partial stop Potentiometer wiring
RE7-PE, PP RE7-PM, PD
Z1
B1 B2 A1 B1 B2 A1
B1 B2 A1 Y1 X1 Z2
A2
Z2 Z2
A2 A2
A2
Wiring precautions
X1 or Y1 or Z1
Z2
A2
No galvanic insulation between supply terminals A1, A2, B1, B2 and control inputs X1, Y1, Z1, Z2.
(1) a or c 42& 48 V: RE7-PP.
Setting-up procedure
1 Potentiometer for fine adjustment of the time delay, graduated in % of range max. setting 2.
2 10-position timing range selector :
1 0.05& 1 s 0.5& 10 s 5& 100 s 1.5& 30 min 1.5& 30 h
4
0.15& 3 s 1.5& 30 s 15& 300 s 15& 300 min 15& 300 h
2
3 Switch for converting the second changeover contact to instantaneous mode (RE7-PP13BU and PD13BU).
3
4 LEDs, depending on the model:
- Green LED: flashes during the time delay period (except for the first 2 timing ranges), permanently on
outside the time delay period
- Yellow LED 1: on when 1st relay is energised
- Yellow LED 2: on when 2nd relay is energised
Adjustment of the time delay
1 40
- Select the timing range immediately greater than the time required using selector switch 2.
Example: required time 12 s; range selected 30 s.
2 30 s x. %
- Using potentiometer 1 display the required time as a % of value 2.
t x 100 12 x 100
1 =       i.e.        = 40
2 30
28454/3
Te
B1
A1
B1
A1
B1
A1
B1
A1
18
15
16
A2
B2
18
15
28
25
16
26
A2
B2
18
15
28
25
16
18
15
16
26
A2
A2
B2
(24)
(21)
(22)
(22)
(24)
(21)
c
110 & 240 V
z 42& 48 V
z 24 V
c
110 & 240 V
z 42& 48 V
z 24 V
c
110 & 240 V
(1)
z 24 V
Supply
Zelio Time timing relays
Characteristics : Relay output, width 22.5 mm, universal
pages 28450/2 and 28450/3
Flashing relays
Dimensions :
page 28458/2
Schemes :
Functions, references
page 28458/2
Setting-up :
page 28458/3
Flashing relays
Time delay adjustable from 0.05 s to 300 h in 10 ranges (see setting-up procedure on page opposite).
Symmetrical flashing relay Asymmetrical flashing relay
RE7-CL, CP Start during the ON period Start during the OFF period
RE7-CV (X2Z2 linked) RE7-CV (X2Z2 not linked)
Supply Supply Supply
de-energised
energised
15/18 (25/28) 15/18 (25/28) C/O
open C/O C/O
15/16 (25/26) 15/16 (25/26)
closed
t t ta tr
tr ta
t, t1 and t2 : adjustable time delays
ts: partial stop time
t : flashing time
ta: On-delay period
External control for Conversion of second changeover contact
tr: Off-delay period
partial stop of time delay to instantaneous mode by means of switch R2
ta = t1 + t2
RE7-CV RE7-CP
tr = t3 + t4
R2 R2
Delay Inst Delay Inst
Supply Supply Supply
C/O 15/18 (25/28) 25/28 21/24
C/O C/O
15/16 (25/26) 25/26 21/22
t t
Partial stop X1Z2
t1 tst2t3 ts t4
Functions Supply Relay Reference Weight
(see diagrams above) voltages output kg
Symmetrical relays with start during OFF period
Flashing relay a or c 24 V 1 C/O RE7-CL11BU 0.150
c 110 & 240 V
Flashing relay a or c 24 V 2 C/O (1) RE7-CP13BU 0.150
External control possible for a or c 42& 48 V
- adjustment of time delay (2) c 110& 240 V
RE7-C
Asymmetrical relay with separate adjustment of On-delay and Off-delay
Flashing relay a or c 24 V 1 C/O RE7-CV11BU 0.150
External control possible for a or c 42& 48 V
- start period c 110& 240 V
- adjustment of time delays (2)
- partial stop
(1) A switch on the front face of the relay allows the second changeover contact to be used in instantaneous mode.
(2) By external potentiometers, to be ordered separately. If external potentiometers are fitted, the internal potentiometers
are automatically disconnected.
28455/2
Te
Zelio Time timing relays
Relay output, width 22.5 mm, universal
Flashing relays
Characteristics :
pages 28450/2 and 28450/3
References :
Schemes, setting-up
page 28455/2
Dimensions :
page 28458/2
Schemes
Terminal blocks
RE7-CL11BU RE7-CP13BU RE7-CV11BU
A1 15 B1
A1 15 B1 A1 15 B1
Z1 25 (21) B2
Z1 Z3 B2
28 (24) 26 (22) Z2
X1 X2 Z2
18 16 A2
18 16 A2 18 16 A2
Recommended application schemes (for other schemes: see page 28458/2)
Start on energisation Start period selection External control of partial stop
RE7-CV RE7-CV
B1 B2 A1
B1 B2 A1 X2 B1 B2 A1
X1
(2)
Z2
A2 Z2
A2
A2
Potentiometer wiring Potentiometer wiring Wiring precautions
RE7-CV RE7-CP
Z3 Z1 X1 or Y1 or Z1
Z1 Z2
A2
Z2
A2
Z2
A2
(3) (4)
No galvanic insulation between supply terminals A1, A2, B1, B2 and control inputs X1, Y1, Z1, Z2.
(1) a or c 42& 48 V: RE7-CP13BU and RE7-CV11BU.
(2) Start during ON period: X2Z2 connected. Start during OFF period: X2-Z2 not linked.
(3) Off-delay adjustment (tr) (contact 15/16 closed).
(4) On-delay adjustment (ta) (contact 15/18 closed).
Setting-up procedure
Symmetrical Asymmetrical
flashing relay flashing relay
1 Potentiometer for fine adjustment of the time delay in % of range max. setting 2.
2 10-position timing range selector :
4
1 0.05& 1 s 0.5& 10 s 5& 100 s 15& 300 min 1.5& 30 h
1
4
A
]
0.15& 3 s 1.5& 30 s 15& 300 s 1.5& 30 min 15& 300 h
2
2
1
B A Adjustable On-delay (ta).
]
2
3
B Adjustable Off-delay (tr).
3 Switch for converting the second changeover contact to instantaneous mode (RE7-CP13BU).
4 LEDs, depending on the model :
- Green LED: flashes during the time delay period, permanently on outside the time delay period
- Yellow LED 1: on when 1st relay is energised
- Yellow LED 2: on when 2nd relay is energised
Adjustment of the time delay
1 40
- Select the timing range immediately greater than the time required using selector switch 2.
Example: required time 12 s; range selected 30 s.
2 30 s x. %
- Using potentiometer 1 display the required time as a % of value 2.
t x 100 12 x 100
1 =       i.e.        = 40
2 30
28455/3
Te
(21)
B1
A1
B1
A1
B1
A1
16
18
15
26
28
25
A2
B2
18
15
16
16
18
15
A2
B2
A2
(22)
(24)
c
110 & 240 V
z 42 & 48 V
z 24 V
c
110 & 240 V
z 42& 48 V
z 24 V
c
110 & 240 V
(1)
z 24 V
Supply
Zelio Time timing relays
Characteristics : Relay output, width 22.5 mm, universal
pages 28450/2 and 28450/3
Timing relays for star-delta starting
Dimensions :
page 28458/2
Schemes :
Functions, references
page 28458/2
Setting-up :
page 28458/3
Timing relays for star-delta starters (1)
Time delay adjustable from 0.05 s to 300 h in 10 ranges (see setting-up procedure on page opposite).
Timing relays for star-delta starters
With double On-delay With contact for switching to star connection
RE7-YA RE7-YR
de-energised Supply Supply
energised
C/O1 15/18 C/O1
17/18
15/16
open
C/O2
17/28
closed
C/O2 25/28
25/26 star
t: adjustable time delay (star) K1
star K1 delta
K3
delta K3 t 50 ms
t 50 ms
Functions Supply Output Reference Weight
(see diagrams below) voltages relay kg
With double On-delay a or c 24 V 2 C/O RE7-YA12BU 0.150
a or c 42& 48 V
c 110& 240 V
RE7-Y
With contact for switching a or c 24 V 2 C/O RE7-YR12BU 0.150
to star connection a or c 42& 48 V with common
1 c 110& 240 V point
(1) Adjustable time delay for operation in star connection and and fixed (50 ms) for switching from star to delta connection
to ensure sufficient breaking time.
28456/2
Te
Zelio Time timing relays
Relay output, width 22.5 mm, universal
Timing relays for star-delta starting
Characteristics :
pages 28450/2 and 28450/3
References :
Schemes, setting-up
page 28456/2
Dimensions :
page 28458/2
Schemes (Star-delta starter application)
Power scheme Control schemes
RE7-YA12BU Star-delta function with double On-delay timing
F3 Terminal block RE7-YA
A1 15 B1
25 B2
F2
S1
K1
28 26 Z2
K2 K3
18 16 A2
S2
K2
K1
14 13
K1T K1T
F2
W1 V2
K3 K1
V1 M1 U2
3
K1 K1T K2 K3
U1 W2
K1T = RE7-YA relay
YN "
Power scheme Control schemes
1
RE7-YR12BU Star-delta function with contact for switching to star connection
Terminal block RE7-YR
F3
A1 17 B1
17 B2
F2
S1
K1
28 26 Z2
K2 K3
K2
18 16 A2
S2
K1T K2 K1
F2
W1 V2
K3 K1
V1 M1 U2
3
U1 W2 K1T K1 K3 K2
K1T = Relay RE7-YR
Y " N
No galvanic insulation between supply terminals A1, A2, B1, B2 and supply terminal Z2.
This terminal must therefore never be used (factory setting).
Setting-up procedure
1 Potentiometer for fine adjustment of the time delay, graduated in % of range max. setting 2.
2 10-position timing range selector :
1 0.05& 1 s 0.5& 10 s 5& 100 s 1.5& 30 min 1.5& 30 h
3
0.15& 3 s 1.5& 30 s 15& 300 s 15& 300 min 15& 300 h
2
3 LEDs, depending on model :
- Green LED: flashes during the time delay period (except the first 2 timing ranges), permanently on
outside the time delay period
- Yellow LED 1: on when 1st relay is energised
- Yellow LED 2: on when 2nd relay is energised
Adjustment of the time delay
1 40
- Select the timing range immediately greater than the time required using selector switch 2.
Example: required time 12 s; range selected 30 s.
2 30 s x. %
- Using potentiometer 1 display the required time as a % of value 2.
t x 100 12 x 100
1 =       i.e.        = 40
2 30
28456/3
Te
L1
L2
L3
B1
A1
18
15
28
25
16
26
A2
B2
2
1
4
3
6
5
2
1
4
3
6
5
2
1
2
1
4
3
4
3
6
5
6
5
A2
A1 21
22 15
16
14
13 22
21 96
95
A2
A1
A2
A1
A2
A1 21
22 25
28
13
14
L1
L2
L3
17
B1
A1
18
28
16
26
A2
B2
2
1
4
3
6
5
2
1
4
3
6
5
14
13 22
21 96
95
14
13
2
1
2
1
4
3
4
3
6
5
6
5
A2
A1
A2
A1 21
22 18
17
54
53
A2
A1 21
22 28
17
A2
A1
14
13
Zelio Time timing relays
Relay output, width 22.5 mm, universal
Multifunction relays
Functions, references
Multifunction relays
Adjustable time delay from 0.05 s to 300 h in 10 ranges (see setting-up procedure on page opposite).
On-delay relay Pulse on energisation relay Flashing relay with
RE7-ML, MY with start on energisation start during the ON period
1
RE7-ML, MY RE7-ML, MY
de-energised
Supply Supply Supply
energised
open
C/O 15/18 (25/28) C/O 15/18 (25/28) C/O 15/18 (25/28)
closed
15/16 (25/26) 15/16 (25/26)
15/16 (25/26)
t: adjustable time delay
t t t t
t = t1 + t2 + t3
ts: partial stop time
Flashing relay with Off-delay relay Pulse on energisation relay with
start during the OFF period RE7-ML, MY start on opening of the
1
RE7-ML, MY external control contact
RE7-ML, MY
Supply Supply Supply
Y1Z2 Y1Z2
Start
Start
C/O 15/18 (25/28)
15/16 (25/26) 15/18 (25/28) C/O 15/18 (25/28)
C/O
15/16 (25/26) 15/16 (25/26)
t t
t
t
Relay for star-delta starters with: External control for External control for
double On-delay timing contact for switching to star start of time delay partial stop of time delay
1
RE7-MY connection RE7-MY (example on On-delay function) (1) (example on pulse on energisation
RE7-ML, MY relay) (1)
RE7-ML, MY
Supply Supply Supply Supply
C/O1
C/O1 15/18 17/18
15/16 (Y1Z2) Partial stop X1Z2
Start
C/O2
17/28
25/28
C/O
15/18
25/26 star 15/18 C/O
15/16 15/16
delta
star
t t1 ts t2 ts t3
t 50 ms
delta
t
t 50 ms
1 1
6 function relay , , , ,
Functions (see diagrams Supply Relay Reference Weight
above) voltages output kg
On-delay relay a or c 24 V 1 C/O RE7-ML11BU 0.150
Off-delay relay a or c 42& 48 V
Pulse on energisation relay c 110& 240 V
- start on energisation
- start on opening of remote
control contact
Flashing relay with start during the OFF period
Flashing relay with start during the ON period
External control possible for:
- start of time delay
- partial stop of time delay
- adjustment of time delay (2)
RE7-MY
1 1 1
8 function relay , , , , , ,
As for 6 function relay (3) + a or c 24 V 2 C/O (4) RE7-MY13BU 0.150
Relay for star-delta c 110 & 240 V
starting
- with double On-delay timing
- with contact for switching
to star connection a or c 24& 240 V 2 C/O (4) RE7-MY13MW 0.150
(1) For use on other functions, please see the diagrams relating to the single function products.
(2) By external potentiometer, to be ordered separately. If external potentiometer is fitted, the internal potentiometer is
automatically disconnected.
(3) Except control of partial stop of time delay for RE7-MY13BU.
(4) A switch on the front face of the relay allows the second changeover contact to be used in instantaneous mode.
28457/2
Te
Zelio Time timing relays
Relay output, width 22.5 mm, universal
Multifunction relays
Schemes, setting-up
Schemes
Terminal blocks
RE7-ML11BU RE7-MY13BU RE7-MY13MW
A1 15 B1 A1 15 B1 A1 15 Y1
Z1 B2 Z1 25 (21) Y1 Z1 25 (21) X1
X1 Y1 Z2 28 (24) 26 (22) Z2 28 (24) 26 (22) Z2
18 16 A2 18 16 A2 18 16 A2
Recommended application schemes
Start on energisation Start by external control External control of partial stop
B1 B2 A1
B1 B2 A1 Y1 B1 B2 A1
X1
A2 Z2 Z2
A2
A2
Potentiometer wiring Wiring precautions
Z1
X1 or Y1 or Z1
Z2
A2
Z2
A2
No galvanic insulation between supply terminals A1, A2, B1, B2 and control inputs X1, Y1, Z1, Z2.
(1) c 110& 240 V: RE7-ML11BU or RE7-MY13BU, a or c 24& 240 V: RE7-MY13MW.
(2) c or a 42& 48 V: RE7-ML11BU.
(3) c or a 24 V: RE7-ML11BU or RE7-MY13BU.
Setting-up procedure
1 Potentiometer for fine adjustment of the time delay, graduated in % of range max. setting 2.
2 10-position timing range selector:
0.05& 1 s 5& 100 s 15& 300 min
1 0.15& 3 s 15& 300 s 1.5& 30 h
5
0.5& 10 s 1.5& 30 min 15& 300 h
2
1.5& 30 s
4
3 10-position function selector switch (positions which are not used have no marking; the output relay(s)
3
stay(s) in the Off position, whatever the control instructions are).
4 Switch for converting the second changeover contact to instantaneous mode (depending on model).
5 LEDs, depending on the model:
- Green LED: flashes during the time delay period (except for the first 2 timing ranges), permanently on
outside the time delay period.
- Yellow LED 1: on when 1st relay is energised.
- Yellow LED 2: on when 2nd relay is energised.
Adjustment of the time delay
1 40
- Select the timing range immediately greater than the time required, using selector switch 2.
Example: required time 12 s; range selected 30 s.
2 30 s x. %
- Using potentiometer 1 display the required timing value as a % of value 2.
t x 100 12 x 100
1 =       i.e.        = 40
2 30
28457/3
Te
B1
A1
B1
A1
16
18
15
18
15
28
25
18
15
28
25
16
26
16
26
A2
A2
A2
A1
(22)
(24)
(21)
(22)
(24)
(21)
(1)
(1)
(1)
(2)
(2)
(2)
(3)
(3)
(3)
Supply
Zelio Time timing relays
Relay output, width 22.5 mm, universal
Characteristics :
pages 28450/2 and 28450/3
References :
Dimensions, mounting
pages 28451/2 to 28457/2
Setting-up :
page 28458/3
RE7
Dimensions Rail mounting
80 22,5 89,5
82
Screw fixing
4
28458/2
Te
78
6
78
6
Zelio Time timing relays
Relay output, width 22.5 mm, universal
Characteristics :
pages 28450/2 and 28450/3
References :
Schemes
pages 28451/2 to 28457/2
Dimensions :
page 28458/2
Schemes :
pages 28451/3 to 28458/2
Schemes
Control of several relays with a single external control contact Connection of Telemecanique 3-wire NPN or PNP sensor
+
24 A1, B1 or B2
A1, B1 or B2 A1, B1 or B2 A1, B1 or B2
BN
NPN
or
Y1 or X1 Y1 or X1 Y1 or X1
Y1
BK
48 V PNP
Z2 Z2 Z2
A2 A2 A2 A2 Z2 BU

It is advisable to follow the recommended wiring schemes detailed above and on previous pages. However, the connections below are possible if the restrictions
given are taken into account.
Connection of an external control contact without using terminal Z2:
- possible on all RE7 relays with external control option except RE7-RA11BU
- d.c. supply only
+ +
A1, B1 or B2 A1, B1 or B2
Y1 or X1 Y1 or X1
Z2 Z2
A2 A2
 
Connection of a Telemecanique 3-wire NPN or PNP sensor without using terminal Z2:
- only possible on relay RE7-iiiiBU
- d.c. supply only
+ +
BN BN
B1B2 B1B2
24 24
Y1 Y1
BK NPN BK PNP
or or
A2 Z2 BU A2 Z2 BU
48 V 48 V
 
28458/3
Te
Supply
Zelio Time timing relays
Relay output, width 22.5 mm, optimum
References :
pages 28462/2 and 28463/2 General characteristics
Dimensions :
page 28464/2
Schemes, setting-up :
pages 28462/3, 28463/3 and 28464/3
Presentation
The RE8 range of relays is designed for simple and repetitive applications, providing basic functions.
Each relay comprises:
- a single timing range,
- a C/O output relay.
These products have a transparent, hinged flap on their front face to prevent any accidental alteration of the settings.
This flap can be directly sealed.
Environment
Conforming to standards IEC 61812-1, EN 61812-1
Product approvals CSA, GL pending, UL
Ł marking Zelio Time timing relays conform to European regulations
relating to Ł marking
Ambient air temperature Storage C - 40& + 85
around the device Operation C - 20& + 60
Permissible relative humidity range Conforming to IEC 60721-3-3 15& 85 % Environmental class 3K3
Vibration resistance Conforming to IEC 6068-2-6, 10 to 55 Hz a = 0.35 ms
Shock resistance Conforming to IEC 6068-2-27 15 gn - 11 ms
Degree of protection Casing IP 50
Terminals IP 20
Degree of pollution Conforming to IEC 60664-1 3
Overvoltage category Conforming to IEC 60664-1 III
Rated insulation voltage Conforming to IEC V 250
Conforming to CSA V 300
Test voltage for Dielectric test kV 2.5
insulation tests Shock wave kV 4.8
Voltage limits Power supply circuit 0.9& 1.1 Uc
Frequency limits Power supply circuit Hz 50/60 ą 5 %
Disconnection value Power supply circuit > 0.1 Uc
Mounting position In relation to normal vertical Any position
without derating mounting plane
Connection Flexible cable without cable end mm2 2 x 2.5
maximum c.s.a. Flexible cable with cable end mm2 2 x 1.5
Tightening torque N.m 0.6& 1.1
Immunity to electromagnetic interference (EMC) (Application class 2 conforming to EN 61812-1)
Electrostatic discharge Conforming to IEC 61000-4-2 Level 3 (6 kV contact, 8 kV air)
Electromagnetic fields Conforming to IEC 61000-4-3 Level 3 (10 V/m)
Fast transients Conforming to IEC 61000-4-4 Level 3 (2 kV)
Shock waves Conforming to IEC 61000-4-5 Level 3 (2 kV)
Radiated and CISPR11 Group 1 class A
conducted emissions CISPR22 Class A
Consumption
Consumption ca
24 V 110 V 240 V 380 V 415 V 24 V
RE8-TA, RA, CL, PE, PU, PT VA 0.7 1.8 8.5   W 0.5
RE8-YG, RB VA 0.9 2.5 13   W 0.5
RE8-YA VA 0.9 2.5 13 8 9 W 0.7
28461/2
Te
Zelio Time timing relays
Relay output, width 22.5 mm, optimum
References :
pages 28462/2 and 28463/2 General characteristics (continued)
Dimensions :
page 28464/2
Schemes, setting-up :
pages 28462/3, 28463/3 and 28464/3
Time delay characteristics
Setting accuracy As % of the full scale value ą 20 %
Repeat accuracy <1%
Influence of voltage In the voltage range, 0.9& 1.1 Un < 2.5 %
Influence of temperature < 0.2 %/C
Immunity to
micro-breaks ms 3
Minimum control pulse ms 26 (except RE8-YG: 60)
Reset time ms 50
Output circuit characteristics
Maximum switching voltage V z 250
Mechanical durability In millions of operating cycles 20
Current limit Ith A 8
Rated operational limits at 70 C 24 V 115 V 250 V
Conforming to IEC 60947-5-1/1991 AC-15 A 333
and VDE 0660 DC-13 A 2 0.2 0.1
Minimum switching capacity 12 V/10 mA
Contact material Nickel Silver 90/10
Remote control input characteristics
Signal delivered by No-load voltage Supply voltage
control input Y1 Switching current mA < 10
No galvanic insulation between Maximum distance m 50
this input and the power supply Compatibility a 2-wire sensors with leakage current < 1 mA
a.c. load d.c. load
Curve 1 Curve 2 Load limit curve
Electrical durability of contacts on resistive Reduction factor k for inductive loads
load in millions of operating cycles (applies to values taken from the
durability curve opposite)
10 1 300
0,9
200
0,8
0,7
100
1
3
0,6
2
50
0,5
40
1
0,1
30
0,4
20
A
A
0,01 0,3 10
0 1 2 3 4 5 6 7 8 1 0,8 0,6 0,5 0,4 0,3 0,2 0,1 0,2 0,5 1 2 5 10 20
Current broken in A Power factor on breaking (cos ) Current in A
A RE8-RBiiBUTQ A RE8-RBiiBUTQ
1 L/R = 20 ms
Example: 2 L/R with load protection diode
3 Resistive load
An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current
consumption equal to 0.1 A and cos  = 0.3
+
For 0.1 A, curve 1 indicates a durability of approximately 1.5 million operating cycles.
RE8
As the load is inductive, it is necessary to apply a reduction coefficient k to this number of
cycles, as indicated by curve 2.
K
For cos  = 0.3: k = 0.6

The electrical durability therefore becomes:
1.5 106 operating cycles x 0.6 = 900 000 operating cycles
28461/3
Te
Voltage in V
Reduction factor k
Millions of operating cycles
Zelio Time timing relays
Relay output, width 22.5 mm, optimum
On-delay, Off-delay, flashing relays
Characteristics :
pages 28461/2 and 28461/3
Dimensions :
Functions, references
page 28464/2
Schemes, setting-up :
pages 28462/3 and 28464/3
On-delay relays
On-delay relay
Start on energisation
RE8-TA
de-energised
Supply
energised
open
15/18
C/O
15/16
closed
t
t: adjustable On-delay
Composition Supply Quantity Timing Reference Weight
voltages per pack range (1) kg
1 C/O z 24 V 10 0.1 s& 3 s RE8-TA61BUTQ 0.110
c 110& 240 V 0.1 s& 10 s RE8-TA11BUTQ (2) 0.110
0.3 s& 30 s RE8-TA31BUTQ (2) 0.110
3 s& 300 s RE8-TA21BUTQ (2) 0.110
20 s& 30 min. RE8-TA41BUTQ 0.110
RE8-TA Off-delay relays
Off-delay relay
With control contact Self-powered
RE8-RA RE8-RB
de-energised Supply Supply
energised
Start C/O
open 15/18
15/16
closed
> 80 ms t
C/O
t: adjustable Off-delay 15/18
15/16
t
Composition Supply Quantity Timing Reference Weight
voltages per pack range (1) kg
Control contact
1 C/O z 24 V 10 0.1 s& 10 s RE8-RA11BTQ (2) 0.110
0.3 s& 30 s RE8-RA31BTQ 0.110
3 s& 300 s RE8-RA21BTQ (2) 0.110
c 110& 240 V 10 0.1 s& 10 s RE8-RA11FUTQ (2) 0.110
0.3 s& 30 s RE8-RA31FUTQ 0.110
3 s& 300 s RE8-RA21FUTQ (2) 0.110
20 s& 30 min. RE8-RA41FUTQ 0.110
Self-powered
1 C/O z 24 V 10 0.05 s& 0.5 s RE8-RB51BUTQ 0.110
c 110& 240 V 0.1 s& 10 s RE8-RB11BUTQ 0.110
0.3 s& 30 s RE8-RB31BUTQ 0.110
Flashing relays
Symmetrical
RE8-CL
de-energised Supply
energised
open C/O 15/18
15/16
closed
t t
t = flashing time
Composition Supply Quantity Timing Reference Weight
voltages per pack range (1) kg
1 C/O z 24 V 10 0.1 s& 10 s RE8-CL11BUTQ 0.110
c 110& 240 V
(1) For easier adjustment, it is preferable to set the time delay between the maximum value in the range and one tenth
of this value.
Example: RE8-TA11BUTQ timing range 0.1 s& 10 s, recommended use 1 s& 10 s.
(2) Also available in pack of one; delete TQ from the end of the reference. Example: RE8-TA11BU.
28462/2
Te
Zelio Time timing relays
Relay output, width 22.5 mm, optimum
On-delay, Off-delay, flashing relays
Characteristics :
pages 28461/2 and 28461/3
References :
Schemes, setting-up
page 28462/2
Dimensions :
page 28464/2
Schemes
Terminal blocks
RE8-TA, CL RE8-RA RE8-RB
A1 15 B1 A1 15 B1
A1 15 Y1
18 16 A2 18 16 A2
18 16 A2
Recommended application schemes
RE8-TA, RB, CL RE8-RA
+
Start
A1
Y1
B1 A2
A2
A1

Setting-up
1 Potentiometer for fine adjustment of the time delay, graduated in % of range max. setting 2.
2 Marking of maximum time delay value.
1
3 LEDs, depending on the models :
3
- Yellow LED: illuminates when the output relay is energised,
2
- Green LED: illuminates when the RE8 is energised.
Adjustment of the time delay
- The maximum value of the timing range is printed on the product, 2.
1 80
Example: RE8-TA61BUTQ; maximum time delay: 3 s.
- Time required 2.4 s; using potentiometer 1 set the value of the time delay required as a % of value 2 :
2 3 s x. %
t x 100 2.4 x 100
value 1 =       =         = 80
2 3
28462/3
Te
B1
A2
B1
A2
16
18
15
A1
16
18
15
A1
16
18
15
A1
A2
a
24 V
c
110 & 240 V
c 24 V
c
110 & 240 V
z 24 V
Zelio Time timing relays
Relay output, width 22.5 mm
Pulse on energisation relays, relays for star-delta starters
Characteristics :
pages 28461/2 and 28461/3
Dimensions :
Functions, references
page 28464/2
Schemes, setting-up :
pages 28463/3 and 28464/3
1
Pulse on energisation relays
Start on Start on opening of Start on
energisation external control contact de-energisation
RE8-PE RE8-PD RE8-PT
Supply
Supply Supply
de-energised
energised
C/O 15/18 Start
Y1A1 C/O
open 15/18
15/16
15/16
closed
t t < t
C/O
15/18
t: pulse time
15/16
> 80 ms
t
Composition Supply Quantity Timing Reference Weight
voltages per pack range (1) kg
On energisation
1 C/O z 24 V 10 0.1 s& 10 s RE8-PE11BUTQ 0.110
c 110& 240 V 0.3 s& 30 s RE8-PE31BUTQ 0.110
3 s& 300 s RE8-PE21BUTQ 0.110
By control contact
1 C/O z 24 V 10 0.1 s& 10 s RE8-PD11BTQ 0.110
0.3 s& 30 s RE8-PD31BTQ 0.110
RE8-PE 3 s& 300 s RE8-PD21BTQ 0.110
c 110& 240 V 10 0.1 s& 10 s RE8-PD11FUTQ 0.110
0.3 s& 30 s RE8-PD31FUTQ 0.110
3 s& 300 s RE8-PD21FUTQ 0.110
On de-energisation
1 C/O z 24 V 10 0.05 s& 1 s RE8-PT01BUTQ 0.110
c 110& 240 V
Timing relays for star-delta starters
Timing relays for star-delta starters
With contact for switching to star connection With double On-delay period
RE8-YG (2) RE8-YA
de-energised Supply Supply
energised
15/18 15/16
N/C
15/16
open
25/28
N/O
closed
star
t 80 ms
t: adjustable time delay (star)
delta
t 50 ms
Composition Supply Quantity Timing Reference Weight
voltages per pack range (1)
1 C/O z 24 V 10 0.1 s& 10 s RE8-YG11BUTQ 0.110
c 110& 240 V 0.3 s& 30 s RE8-YG31BUTQ 0.110
3 s& 300 s RE8-YG21BUTQ 0.110
1 N/C + 1 N/O z 24 V 10 0.3 s& 30 s RE8-YA32BTQ 0.110
c 110& 240 V 10 0.3 s& 30 s RE8-YA32FUTQ 0.110
c 380& 415 V 10 0.3 s& 30 s RE8-YA32QTQ 0.110
(1) For easier adjustment, it is preferable to set the time delay between the maximum value in the range and one tenth
of this value.
Example: RE8-PE11BUTQ timing range 0.1 s& 10 s, recommended use 1 s& 10 s.
(2) Correct operation of the star-delta starter is only possible if the wiring scheme on page 28463/3 is strictly complied
with.
28463/2
Te
Zelio Time timing relays
Relay output, width 22.5 mm, optimum
Pulse on energisation relays, relays for star-delta starters
Characteristics :
pages 28461/2 and 28461/3
References :
Schemes, setting-up
page 28463/2
Dimensions :
page 28464/2
Schemes
Terminal blocks
RE8-PE RE8-PD RE8-PT RE8-YA RE8-YG
A1 15 B1 A1 15 25 A1 15 B1
A1 15 B1 A1 15 Y1
18 16 A2 28 16 A2 18 16 A2
18 16 A2 18 16 A2
Recommended application schemes
Pulse on energisation relays
RE8-PE, PT RE8-PD
+
Start
A1
Y1
B1 A2
A2
A1

Timing relays for star-delta starters
RE8-YG, RE8-YA RE8-YG RE8-YA
 FU1  FU1
 Q1
 Rth  Rth
 S1  S1
 KM2  KM1  S2  KM2
 S2
 KM2  KM3  KM1
 KM1
 KM2  K1T (1)
 KM1
 K1T
 K1T
16 15
 KM3  KM1
 KM3  KM1
 Rth
 KM1  K1T  KM3  KM2  KM1  K1T  KM2  KM3
(1)
(1)
L L
(1) K1T: RE8-YGi1iiTQ (1) K1T: RE8-YA32iiTQ
Note: Correct operation of the star-delta starter associated with the RE8-YG is only possible if the wiring scheme is strictly complied with.
Setting-up
1 Potentiometer for fine adjustment of the time delay, graduated in % of range max. setting 2.
2 Marking of maximum time delay value.
1
3 3 LEDs, depending on the models :
2
- Yellow LED: illuminates when the output relay is energised,
- Green LED: illuminates when the RE8 is energised.
Adjustment of the time delay
- The maximum value of the timing range is printed on the product 2.
1 24
Example: RE8-PE11BUTQ; maximum time delay: 10 s.
- Time required 2.4 s; using potentiometer 1 set the value of the time delay required as a % of value 2:
2 10 s x. %
t x 100 2.4 x 100
value 1 =       =         = 24
2 10
28463/3
Te
B1
A2
B1
A2
B1
A2
18
15
16
A1
16
15
28
25
18
15
16
A1
A2
A1
18
15
16
A1
16
18
15
A1
A2
a
24 V
c
110 & 240 V
c 24 V
c
110 & 240 V
z 24 V
L1
L3
L2
28
25
V2
V1
U2
U1
W2
W1
A2
A1
A2
A1
A2
A1
A2
A1
A2
A1
16
15
A2
A1
A2
A1
A2
A1
Y
Y
Y
Zelio Time timing relays
Relay output, width 22.5 mm, optimum
Characteristics :
pages 28461/2 and 28461/3
Dimensions, mounting
References :
pages 28462/2 and 28463/2
Schemes, setting-up :
pages 28462/3, 28463/3 and 28464/3
RE8
Dimensions
80 22,5
Rail mounting
89,5
82
Screw fixing
4
28464/2
Te
78
6
78
6
Zelio Time timing relays
Characteristics :
Relay output, width 22.5 mm, optimum
pages 28461/2 and 28461/3
References :
pages 28462/2 and 28463/2
Schemes
Dimensions :
page 28464/2
Setting-up :
pages 28462/3 and 28463/3
Control of several relays with a single external control contact
RE8-RA, PD
A1 A1 A1
Y1 Y1 Y1 C
A2 A2 A2
The external control contact C may be an electronic control device, for example a 2-wire sensor. In this case A1-A2 = a 24 V and the control device can only control
up to a maximum of 4 relays.
Connection of a a 2-wire sensor
+
If
A1
Y1
A2

Leakage current (open state) If < 1 mA.
28464/3
Te


Wyszukiwarka

Podobne podstrony:
02 ZELIO CONTROL?TALOGUE
Margit Sandemo Cykl Saga o czarnoksiężniku (02) Blask twoich oczu
t informatyk12[01] 02 101
introligators4[02] z2 01 n
02 martenzytyczne1
OBRECZE MS OK 02
02 Gametogeneza
02 07
Wyk ad 02
r01 02 popr (2)
Instrukcja Programowania Zelio Logic 2 wersja polska
1) 25 02 2012

więcej podobnych podstron