IS 974 LX


IS 974 LX
electronic controllers for  forced air
refrigerating units
This family consist of a main unit called IS MACHINE STATUS MENU requested and (if the correct password is
and an expansion module called EWEM, To access the  Machine Status menu entered) the label of the first folder in the
connected together with a telephone Press and quickly release the  set key. programming menu will follow.
cable. If alarms are not present, the label  SEt To enter the folder, press  set . The label
appears. By using the  UP and  DOWN of the first visible parameter appears. To
keys you can scroll through the other fold- scroll through the other parameters, use
USER INTERFACE
ers in the menu: the  UP and  DOWN keys; to change the
The user has a display and four keys for
-AL: alarm folder (if present); parameter, press and release  set , then
controlling status and programming of the
-Pb1: probe 1 value folder; set the desired value using the  UP and
instrument.
-Pb2: probe 2 value folder  DOWN keys, and confirm with the  set
KEYS AND MENUS -SEt: Setpoint setting folder. key to move to the next parameter.
Set Setting PLEASE NOTE: It is strongly recommended
UP key Scrolls through the menu
Access the  Machine Status menu by to switch off and switch on again the con-
items Increases the values
pressing and quickly releasing the  set troller anytime parameters have been
Activates manual def. function
key. The label of the  SEt folder appears. changed to prevent malfunctioning on
DOWN key Scrolls through the menu items
To display the Setpoint value press the configuration and/or ongoing timings.
Decreases the values
 set key again.
Programmable by parameter
The value appears on the display. PASSWORD
fnc key ESC function (exit) To change the Setpoint value, use the  UP The passwords  PA1 and  PA2 allow
fnc
Programmable by parameter
and  DOWN keys within 15 seconds. access respectively to level 1 and level 2
If the parameter is LOC = y the Setpoint parameters. In the standard configuration
set key Accesses the setpoint
set Accesses the menus cannot be changed. passwords are not present.
Confirms the commands
Alarm on To enable them and assign them the
Displaying the alarms (if present)
If alarm condition exists, when accessing desired value, access the  Programming
The  Machine Status menu the  AL fold- menu, within the folder with the  diS
At start-up the instrument performs a er label appears (see the  Diagnostics label. If passwords are enabled, they will
Lamp Test; for few seconds the display and section). be requested:
the leds blink, in order to verify their Displaying Probes - PA1 at the entrance of the
integrity and correct operation. The instru- By pressing the  set key when the appro-  Programming menu (see the
ment has two main menus: the  Machine priate label appears, the value of the  Programming Menu section);
Status and  Programming menu. probe associated to it is displayed. - PA2 within the folder with the  Cnf
label containing level 1 parameters.
ACCESSING AND USING MENUS PROGRAMMING MENU
Resources are arranged in a menu, which To access the  Programming menu, press MANUAL ACTIVATION OF THE
can be accessed by pressing and quickly the  set key for more than 5 seconds. If DEFROSTING CYCLE
releasing the  set key ( Machine Status specified, the level 1 access PASSWORD To manually activate the defrosting cycle,
menu) or by holding down the  set key will be requested (see parameter  PA1 ) press the  UP key for 5 seconds.
for more than 5 seconds ( Programming and (if the password is correct) the label If defrosting conditions are not present,
menu). of the first folder will follow. If the pass- (for example the evaporator probe
To access the contents of each folder, indi- word is wrong, the display will show the temperature is higher than defrost stop
cated by the relevant label, just press the PA1 label again. temperature or if parameter OdO`"0), the
 set key once. To scroll other folders, use the  UP and display will blink three (3) times, in order
You can now scroll through the contents  DOWN keys; the folders contain the to indicate that the operation will not
of each folder, modify it or use its func- level 1 and 2 parameters. The level 2 para- be performed.
tions. If you do not use the keyboard for meters may be protected by a second
over 15 seconds (time-out) or if you press password (see  PA2 parameter). If speci- COPY CARD
the  fnc key once, the last value shown fied, level 2 parameters are hidden to The Copy Card is an accessory connected
on the display is confirmed and you return user; at the entrance of the  Cnf folder to the TTL serial port which allows pro-
to the previous screen mask. the level 2 access PASSWORD will be gramming quickly the instrument parame-
ters (upload and download parameter s
LED map). The operation is performed as fol-
lows:
Position Related Function Status
Format
Compressor or relay 1 ON when the compressor is started up; blinking in case of delay,
This command allows copy card formatting,
protection or blocked enabling
an operation necessary in case of first use
or to copy maps with different models.
Defrost ON when defrosting; blinking in case of manual
enabling
Warning: if the copy card has been pro-
grammed, using the  Fr the data entered
Alarm ON when the alarm is enabled; blinking when the alarm is silenced
are erased. This operation cannot be can-
celled.
Fans ON when the fan is working
ELECTRICAL
Upload The error condition of the probe 1 (ther-
This operation loads the programming mostat) causes the following:
WIRING
parameters from the instrument. " the code E1 is displayed
Download " the compressor is activated as indicated Attention! Never work on electrical con-
This operation downloads to the instru- by the "On" and "Off" parameters if pro- nections when the machine is switched on.
ment the programming parameters. grammed for the duty cycle or: The instrument is equipped with screw ter-
The operations are performed accessing minal boards for connection of electrical
Ont Oft Compressor output
the folder identified by the  FPr label and cables with a diameter of 2.5 mm2 (one
0 0 OFF
selecting, according to the case,  UL ,  dL conductor only per terminal for power
0 >0 OFF
or  Fr commands; the operation is con- connections).
>0 0 ON
firmed by pressing the  set key. If the For the capacity of the terminals, see the
>0 >0 D.C.
operation is successful an  y is displayed, label on the instrument.
on the contrary, if it fails a  n will be dis- The relay contacts are voltage free. Do not
played. The error condition of the probe 2 (evap- exceed the maximum current allowed; in
Download  from reset (instrumennt orator) causes the following: case of higher loads, use an appropriate
OFF " viewing E2 code on the display contactor. Make sure the power supply
Connect the coy card with the instrument " end of defrost because of time-out voltage complies with the one required by
OFF (not under voltage). Other signalling alarm are not shown on the instrument.
When the instrument is switched on the the instrument display, but from the In 12V versions the power supply must be
programming parameters will be down-  Machine Status menu within the  AL provided by a security transformer with
loaded into the instrument; after the folder. the protection of a delayed 250 mA fuse.
lamp-test the diplay will show for about 5 Probes have no connection polarity and
seconds: MINIMUM AND MAXIMUM TEMPERA- can be extended using a regular bipolar
" label dLY if copy operation successful TURE ALARMS cable (note that the extension of the
" label DLn if not Regulation of the minimum and maximum probes affects the EMC electromagnetic
PLEASE NOTE: temperature alarms refers to the thermo- compatibility of the instrument: pay
" after the download operation the instru- stat probe. extreme attention to wiring).
ment will immediately work with the new The temperature limits defined by the Probe cables, power supply cables and the
parameters map setting.  HAL (maximum temperature alarm) and TTL serial cables should be distant from
 LAL parameters (minimum temperature power cables.
TELEVIS SYSTEM alarm) are in absolute temperature value.
The link with the Televis system can go When an alarm status occurs, if no alarm
through the serial port TTL (the BUS exclusion phases are underway (see alarm
CONDITIONS OF USE
ADAPTER 100 TTL RS-485 interface module
exclusion parameters), the alarm set icon
must be used).
is lit up and the buzzer, and/or the relay PERMITTED USE
In order to configure the instrument for
configured as an alarm, is activated. The For safety reasons the instrument must be
this purpose you must access the folder
occurrence of this alarm does not in any- installed and used according to the
identified by the  Add label and use the
way effect the control activities in instruction provided and in particular,
parameters  dEA and  FAA .
progress. This alarm status can be viewed under normal conditions, parts bearing
in the  AL folder with AH1-AL1 labels. dangerous voltage levels must not be
KEYBOARD LOCKING accessible.
The instrument includes a facility for dis- DISPLAY ALARM
The device must be adequately protected
abling the keyboard, by programming the AH1 High temperature alarm (referred to
from water and dust as per the application
the thermostat probe or probe 1)
 Loc parameter (see folder with  diS and must also only be accessible via the
AL1 Low temperature alarm (referred to
label). If the keyboard is locked, you can use of tools (with the exception of the
the thermostat probe or probe 1)
still access the programming menu by Ad2 End of defrost due to time-out frontlet).
EA Esternal alarm
pressing the  set key. The device is ideally suited for use on
oPd Open door alarm
The Setpoint can also be viewed. household appliances and/or similar refrig-
To silence alarms press any key.
eration equipment and has been tested
If silenced the LEDs will blink
Alarms are in absolute value or related to Setpoint
with regard to the aspects concerning
DIAGNOSTICS
and (considered as the distance from the Setpoint
European reference standards on safety. It
itself) depending on Att parameter.
The alarm condition is always signalled by is classified as follows:
the buzzer (if present) and by the led of " according to its manufacture: as an auto-
the alarm icon matic electronic control device to be
The alarm signal produced by a faulty incorporated by independent mounting;
INSTALLATION
thermostat probe (referred to probe 1) " according to its automatic operating fea-
is shown as E1 on the instrument display The instrument is designed for panel tures: as a 1 B-type operated control type;
The alarm signal produced by a faulty mounting. Make a hole of 29x71 mm, " as a Class A device in relation to the cat-
evaporator probe (probe 2) is shown as E2 insert the instrument and fix it using the egory and structure of the software
on the instrument display. brackets provided. Do not mount the
instrument in humid and/or dirty places; it UNPERMITTED USE
Error table is suitable for use in ordinary polluted Any other use other than that permitted is
places. Ventilate the place in proximity to de facto prohibited. It should be noted
DISPLAY ERROR the instrument colling slits. that the relay contacts provided are of a
E1 Thermostat probe fault practical type and therefore subject to
E2 Evaporator probe fault
fault. Any protection devices required by
product standards or dictated by common
If simultaneous they will appear on display with 2
sense due to obvious safety reasons should
seconds alternation
be applied externally.
IS 974 LX 2/6
LIABILITY AND RESIDUAL TECHNICAL DATA TECHNICAL DATA
RISKS IS 974 LX EWEM 243
Frontal panel protection: IP65.
Invensys Controls Italy S.r.L. shall not be Casing: plastic 4-Din module 70x85 mm
Casing: plastic body in resin type
liable for any damages deriving from: (2.75x3.34").
PC+ABS UL94 V-0, inspection window in
- installation/use other than that pre- Depth: 61 mm (2.40").
polycarbonate, buttons in thermoplastic
Mounting: Din-rail (Omega 3) or surface
scribed and, in particular, that which does
resin.
mounting.
not comply with safety standards anticipat-
Dimensions: frontal panel 74x32 mm,
Connections: telephone connector for the
ed by regulations and/or those given here-
depth 30 mm.
connection with IS 974 LX main module.
in;
Installation: on panel, with drilling tem-
Use temperature:  5& 50 °C.
- use on boards which do not guarantee
plate 71x29 mm (+0.2/ 0.1 mm).
Storage temperature:  30& 75 °C.
adequate protection against electric shock,
Use temperature:  5& 55 °C.
Use environment humidity: 10& 90 % RH
water or dust under the conditions of
Storage temperature.:  30& 85 °C.
(not condensing).
assembly applied;
Use environment humidity: 10& 90 % RH
Storage environment humidity: 10& 90% RH
- use on boards which allow access to dan-
(not condensing).
(not condensing).
gerous parts without the use of tools;
Storage environment humidity: 10& 90% RH
Analog inputs: two NTC or PTC type
- tampering with and/or alteration of the
(not condensing).
(selectable by parameter configurable
products;
Viewing range:  50& 110 (NTC);  50& 140
from display on IS 974 LX main module).
(PTC) °C without decimal point (selectable
Digital outputs: 1 SPST output on 15(12)A
DISCLAIMER
through parameter on 3 digit & 1/2 + mark
250Va relay, 1 SPDT output on 10(7)A
display.
250Va relay and 2 SPST outputs on 8(3)A
This manual and its contents remain the
Analog inputs: two PTC or NTC inputs
250Va relays, configurable.
sole property of Invensys Controls Italy
(programmable by parameter).
Power supply: 230 Va Ä…15%.
s.r.l., and shall not be reproduced or dis-
Digital input : 1 configurable low voltage
tributed without authorization. Although
digital input
great care has been exercised in the
Connections: telephone connector for the Warning: check the power supply specified
preparation of this document, Invensys
connection with EWEM 243 power module, on the instrument label; for relay and
Controls Italy s.r.l., its employees or its
screw connectors for digital input. power supply capacities, contact the Sales
vendors, cannot accept any liability what-
Serial: TTL for connection to Copy Card or Office).
soever connected with its use. Invensys
Televis system.
Controls Italy s.r.l. reserves the right to
Measuring range: from  50 to 140 °C.
make any changes or improvements with-
Accuracy: 0.5% better than end scale + 1
out prior notice.
digit.
Resolution: 1 or 0.1 °C.
Power: 3 VA.
Power supply: from EWEM 243 power
module.
Invensys Controls Italy s.r.l
via dell'Industria, 15 Zona Industriale Paludi
32010 Pieve d'Alpago (BL) ITALY
Telephone +39 0437 986111
Facsimile +39 0437 989066
Internet http:/www.climate-eu.invensys.com
9/2002 eng
cod. 9IS22053
IS 974 LX 3/6
Tab. 1 Parameter Table
PAR. DESCRIPTION RANGE DEFAULT VALUE* LEVEL** U.M.
COMPRESSOR REGULATOR (folder with  CP label)
diF diFferential. Relay compressor tripping differential. The compressor stops on reaching the 0.1...30.0 2.0 1 °C/°F
Setpoint value (as indicated by the adjustment probe), and restarts at temperature value
equal to the Setpoint plus the value of the differential.
Note: the value 0 cannot be assumed.
HSE Higher SEt. Maximum possible setpoint value. LSE..302 99.0 1 °C/°F
LSE Lower SEt. Minimum possible setpoint value. -55.0...HSE -50.0 1 °C/°F
OSP Offset Setpoint: temperature value to be added algebraically to the setpoint in the case -30.0...30.0 0 2 °C/°F
of reduced set enabled (Economy function). It can be activated through digital input or
by a key configured for such use.
Cit Compressor min on time. Minimum compressor activation time before any possible dis- 0...250 0 2 min
abling. If set at 0 it is not active
CAt Compressor mAx on time. Maximum compressor activation time before any possible dis- 0...250 0 2 min
abling. If set at 0 it is not active
dOd digital (input) Open door. Digital input user shut off. y = yes; n = no. Valid for parameter n/y n 2 flag
 H11 = Ä…4 (door switch).
dAd digital (input) Activation delay. Delay time of digital input activation. 0& 255 0 2 min
COMPRESSOR PROTECTIVE DEVICE (folder with  CP label)
Ont (4) On time (compressor). Compressor activation time in the event of faulty probe. If set to 0...250 0 1 min
 1 with Oft at  0 the compressor is always on, while at Oft >0 it functions always
in duty cycle mode.
OFt (4) OFF time (compressor). Compressor in disabled state time in the event of a faulty probe. 0...250 1 1 min
If set to  1 with Ont at  0 the compressor is always off, while at Ont >0
it functions always in duty cycle mode.
dOn delay (at) On compressor. Delay time in activating the compressor relay after switch-on 0...250 0 1 sec
of instrument
dOF delay (after power) OFF. Delay after switch off; the indicated time must elapse between 0...250 0 1 min
switch-off of the compressor relay and the successive switch-on.
dbi delay between power-on. Delay between switch-ons; the indicated time must elapse 0...250 0 1 min
between two successive switch-ons of the compressor.
OdO (!) delay Output (from power) On. Delay time in activating the outputs after switch-on of 0...250 0 1 min
the instrument or after a power failure.
DEFROSTING REGULATOR (folder with  dEF label)
dty defrost type. Type of defrosting. 0/1/2 0 1 flag
0 = electric defrost;
1 = reverse cycle defrost (hot gas);
2 = Free defrost (compressor hot).
dit defrost interval time. Interval between the start of two successive defrosting operations. 0...250 6 1 hours
U.M. Hours (default) /min/sec depending on dt1 parameter (/min/sec)
dt1 defrost time 1. Measure unit for defrosting intervals ( dit parameter). 0/1/2 0 2 flag
0 =  dit parameter in hours;
1 =  dit parameter in minutes;
2 =  dit parameter in seconds.
dt2 defrost time 2. Measure unit for defrosting duration ( dEt parameter). 0/1/2 1 2 flag
0 =  dEt parameter in hours;
1 =  dEt parameter in minutes;
2 =  dEt parameter in seconds.
dCt defrost Counting type. Selection of count mode for the defrosting interval. 0/1/2 1 1 flag
0 = compressor operating hours (DIGIFROST® method);
1 = Real Time  appliance operating time;
2 = compressor stop.
dOH defrost Offset Hour. Start-of-defrosting delay time from start up 0...59 0 1 min
of instrument.
dEt defrost Endurance time. Defrosting time-out; determines duration of 1...250 30 1 min
defrosting. U.M. minutes (default) /hours/sec depending on dt2 parameter (/h/sec)
dSt defrost Stop temperature. Defrost stop temperature (defined by the evaporator -50.0... 150 8.0 1 °C/°F
probe).
dPO defrost (at) Power On. Determines if at the start-up the instrument must enter defrosting n/y n 1 flag
(if the temperature measured by the evaporator allows this operation).
y = yes, starts defrost at start-up; n = no, doesn t start defrost.
tcd time compressor for defrost. Minimum time for compressor On or OFF before defrost. -31...31 0 2 min
If >0 (positive value) the compressor will be ON for tcd minutes; If<0 (negative value)
the compressor will be OFF for tcd minutes. If =0 parameter is disregarded
Cod Compressor off (before defrost). Time for compressor OFF in proximity of the defrost 0& 60 0 2 min
cycle. If a defrost cycle is set within the programmed time for this parameter, the com-
pressor is not started up.
FAN REGULATOR (folder with  FAn label)
FPt Fan Parameter type.  FSt parameter mode. It can be displayed as temperature 0/1 0 2 flag
absolute value or as value related to Setpoint.
0 = absolute; 1 = relative.
FSt Fan Stop temperature. Fan lock temperature; if the value, read by the evaporator probe, -50.0..150.0 2.0 1 °C/°F
is higher than the set value, fans stop.
Fot Fan on-start temperature. Fan starting temperature; if the temperature read by the eva- -50.0..150.0 -50.0 1 °C/°F
porator is lower than the value set for this parameter, fans stay still.
FAd Fan differential. Fan starting differential (see par.  FSt and  Fot ). 1.0& 50.0 2.0 1 °C/°F
Fdt Fan delay time. Delay time in activating fans after a defrost operation. 0...250 0 1 min
dt drainage time. Dripping time. 0...250 0 1 min
dFd defrost Fan disable. Allows to select the evaporator probes exclusion n/y y 1 flag
during defrost. y = yes; n = no.
FCO Fan Compressor OFF. Allows to select compressor fans lock n/y/d.c. y 1 flag
OFF (switched off).
y = fans activated (with thermostat; based on the value read by the defrost probe,
see parameter  FSt );
n = fans off;
dc = duty cycle (by parameters  Fon and  FoF ).
Fod Fan off (with opened) door. Fans activated with opened door. y = yes; n = no. n/y n 2 flag
Allows to select the fans stop when door is open, and the fan re-start when door will be
closed (if they we active). n=fans stop; y=fans unchanged
IS 974 LX 4/6
PAR. DESCRIPTION RANGE DEFAULT VALUE* LEVEL** U.M.
FdC Fan delay Compressor off. Fan stop delay time after compressor stop. In minutes. =0 0..99 0 2 min
function excluded
Fon Fan oFF (in duty cycle). Fan OFF time due to duty cycle 0..99 0 1 min
Fan use with duty cycle mode; valid for FCO = dc and H42=1
FoF Fan oFF (in duty cycle). Fan OFF time due to duty cycle 0..99 0 1 min
Fan use with duty cycle mode; valid for FCO = dc and H42=1
ALARMS (folder with  AL label)
Att Alarm type. Parameter  HAL and  LAL modes, as temperature absolute values or as dif- 0/1 0 2 flag
ferential compared to the Setpoint.
0 = absolute value; 1 = relative value.
AFd Alarm Fan differential. Alarm differential. 1.0...50.0 2.0 1 °C/°F
HAL (5) Higher ALarm. Maximum temperature alarm. Temperature value (with regard to Setpoint) LAL...150.0 50.0 1 °C/°F
which if exceeded in an upward direction triggers the activation of the alarm signal.
LAL (5) Lower ALarm. Minimum temperature alarm. Temperature value (with regard to Setpoint), -50.0...HAL -50.0 1 °C/°F
which if exceeded in a downward direction, triggers the activation of the alarm signal.
PAO (!) Power-on Alarm Override. Alarm exclusion time after instrument switch on, 0...10 0 1 hours
(6) after a power failure.
dAO defrost Alarm Override. Alarm exclusion time after defrost. 0..999 0 1 min
OAO Output (door) Alarm Override. Delay time for temperature alarm signalling after disabling 0& 10 0 2 hours
of digital input (or gate closure). Alarm is only for high-low temperature alarms.
tdO Time-out Door Open. Alarm signalling delay time for gate open. 0& 250 0 2 min
tAO (6) temperature Alarm Override. Temperature alarm signal delay time. 0...250 0 1 min
dAt defrost Alarm time. Alarm for defrost end due to time-out. n/y n 2 flag
n = enables alarm; y = does not enable alarm.
EAL External Alarm Lock. External alarm for regulators stop. Allows the blocking of compres- n/y n 2 flag
sor, defrosting and fan regulators if the digital input (configured as external alarm) is
AOP activated. n = not block; y = block.
Alarm Output Polarity. Polarity of alarm output. 0/1 1 2 flag
0 = alarm activated and output disabled;
1 = alarm activated and output disabled.
dEA (!) COMUNICATION (folder with label  Add )
dEvice Address. Device address: indicates the appliance address to the management pro- 0...14 0 1 num
tocol
FAA (!) FAmily Address. Family address: indicates the appliance family to the management proto- 0...14 0 1 num
col
DISPLAY (folder with  diS label)
LOC (keyboard) LOCk. Keyboard locking. However, you can enter parameter programming n/y n 1 flag
modify them along with the status of this parameter in order to allow keyboard locking.
y = yes; n = no
PA1 PAssword 1. When enabled (value other than 0) it constitutes the access key for 0...250 0 1 num
level 1 parameters.
PA2*** PAssword 2. When enabled (value other than 0) it constitutes the access key 0...255 0 2 num
for level 2 parameters.
ndt number display type. View with decimal point. y = yes; n = no n/y n 1 flag
CA1 CAlibration 1.Calibration 1. Positive or negative temperature value added to the value -12.0...12.0 0 1 °C/°F
read by probe 1, based on  CA parameter settings.
CA2 CAlibration 2.Calibration 2. Positive or negative temperature value added to the value -12.0...12.0 0 1 °C/°F
read by probe 2, based on  CA parameter settings.
CA CAlibration Intervention. Intervention on view offset, thermostat offset or both. 0/1/2 2 2 num
0 = modifies the temperature displayed only;
1 = adds to the temperature used by regulators, not to the temperature displayed, which
stays unchanged.
2 = adds to the temperature displayed that is also used by regulators.
LdL Low display Label. Minimum value the instrument is able to display. -55.0...302 -55.0 2 °C/°F
HdL High display Label. Maximum value the instrument is able to display. -55.0..302 140.0 2 °C/°F
ddL defrost display Lock. Viewing mode during defrosting. 0/1/2 1 1 flag
0 = shows the temperature read by the thermostat probe;
1 = locks the reading on the temperature value read by thermostat probe when
defrosting starts, and until the next time the Setpoint value is reached;
2 = displays the label  deF during defrosting, and until the next time the
Setpoint value is reached.
dro display read-out. Select °C or °F for displaying the temperature read by the probe. 0/1 0 1 flag
0 = °C, 1 = °F. PLEASE NOTE: the switch between °C and °F DO NOT modify setpoint, dif-
ferential, etc. (for example set=10°C become 10°F).
ddd Selection of the value type to be shown on the display. 0/1/2 1 2 num
0 = Setpoint;
1 = probe 1;
2 = probe 2.
CONFIGURATION (folder with  CnF label)
H00 (!) (1) Probe type selection, PTC or NTC. 0 = PTC; 1 = NTC. 0/1 1 1 flag
H02 Time to enable keys, if these are configured for a specific function. 0...15 5 2 sec
H11 (2) Configurability digital inputs/polarity. -5...5 0 2 flag
0 = disabled;
Ä… 1 = defrosting;
Ä… 2 = reduced set;
Ä… 3 = not used;
Ä… 4 = door switch;
Ä… 5 = external alarm.
H21 (!) Configurability digital output 1. (OUT 1) 0...5 1 2 flag
0 = disabled;
1 = compressor;
2 = defrosting;
3 = fans;
4 = alarm;
5 = optional.
H22 (!) Configurability digital output 2. (OUT 3) 0...5 3 2 flag
Same as H21.
H23 (!) Configurability digital output 3. (OUT 2) 0...5 2 2 flag
Same as H21
H24 (!) Configurability digital output 4. (OUT 4) 0...5 4 2 flag
Same as H21
IS 974 LX 5/6
PAR. DESCRIPTION RANGE DEFAULT VALUE* LEVEL** U.M.
H25 (!) Configurability buzzer output. 0...5 4 2 flag
(3) Same as H21.
H31(!) Configurability UP key 0...3 1 2 num
0 = disabled;
1 = defrosting;
2 = optional;
3 = reduced set (economy).
H32 (!) Configurability DOWN key 0...3 0 2 num
0 = disabled;
1 = defrosting;
2 = optional;
3 = reduced set (economy).
H33 (!) Configurability FNC key 0...3 0 2 num
0 = disabled;
1 = defrosting;
2 = optional;
3 = reduced set (economy).
H41 Regulating probe present. n/y y 2 flag
H42 Evaporator probe present. n/y y 1 flag
reL reLease firmware. Device version: read only parameter. / / 1 /
TAb tAble of parameters. Reserved: read only parameter. / / 1 /
COPY CARD (folder with  Fpr label)
UL Up load. Programming parameter transfer from instrument to Copy Card. / / 1 /
dL Down load. Programming parameter transfer from Copy Card to instrument / / 1 /
Fr Format. Erasing all data in the copy card. / / 2 /
NOTA BENE using  Fr parameter (copy card formatting) the data within the copy
card will be lost permenently. The operation cannot be cancelled.
(1) the default value is 1 (NTC input, see the label on the instrument).
(2) WARNING! positive or negative values change polarity; Positive values: active input for on contact; negative values: active input for off contact.
(3) Parameter visible in models with optional buzzer.
(4) Ont e Oft parameters should never be set =0 at the same time
(5) If alarms are related to the Setpoint, HAL parameter should be set to positive values and LAL should be set to negative values
(6) Referred only to low and high temperature alarms
* VALUE column: to be filled manually, with customized settings (if different from the default value).
** LEVEL column: indicates the level of visibility of parameters accessible by PASSWORD (see the related paragraph)
*** PA2 is visible (it will be required, if necessary) at level 1 and can be set (editable) at level 2
(!) WARNING!
" If one or more of these parameters highlighted with (!) are modified, the controlller must be switched off and switched on again to ensure correct operation.
" It is strongly recommended, anyway to switch off and switch on again the controller anytime parameters have been changed to prevent malfunctioning on configuration
and/or ongoing timings
WIRING IS 974 LX
3 - 4 Digital input
IS 974 LX
B
A
A
A TTL input for Copy Card and connection to
to EWEM 243
Televis system
Module
B connection IS 974 LX-EWEM 243
3 4
WIRING EWEM 243
1 - 2 output relay 4 (OUT 4)
1 2 3 4 5 6 11 12
2 - 3 - 4 output relay 2 (OUT 3)
C
5 - 6 output relay 3 (OUT 2)
11 - 12 Power Supply
16 Probe 1 input (thermostat)
17 Probe 2 input (evaporator)
18 common analogue (probes) inputs
EWEM 243
22 - 24 output relay 1 (OUT 1)
B connection IS 974 LX-EWEM 243
B
C RS-485 supply (not used)
to 974 LX
module
NOTE: Default user settings
16 17 18 22 24
IS 974 LX 6/6
Wiring diagram


Wyszukiwarka

Podobne podstrony:
IC 912 LX
ID 974 LX
IS?2 LX
AlphaPC 164 LX stacja robocza w cenie PC
INSTALACJA CZUJKI LX 402 LX 802N
Philips LX 9000R
Przeróbka wycieraczek przedniej i tylnej Škody Felicii Lx
LX 04 day 1 2
ID 985 LX eng 12 02
lx
PHILIPS LX 8200SA
Is4
LX 04 day 2 3

więcej podobnych podstron